56
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Chapter 3
CGCM-DLR Unit Operation
Over-excitation Limit
The Over-excitation limit (OEL) operates in all modes except FCR. The
CGCM-DLR unit senses and limits the field current to prevent field
overheating. When the limit is reached, the limiter function overrides AVR,
VAR, or Power Factor modes to limit field current to the preset level. OEL
operates in the area above the Field Winding Heating Limitation curve in the
generator capability curve.
The generator operates in one of two different states, offline or online. The
generator is offline when it is operating in a constant-voltage mode. The
CGCM-DLR unit is considered online if any of these modes are enabled:
•
Droop (reactive power) compensation
•
Cross current compensation
•
Line drop compensation
Two OEL current levels, high and low, are defined for offline operation as shown
in
. The generator can operate continuously at or below the low OEL
current level and for a time at the high OEL current level that you configure.
Figure 32 - Offline Over-excitation Limiting
FIELD
C
URRENT
TIME IN
S
ECOND
S
High
Current
Time
CONTINUOU
S
0…10 seconds
Low
Current
Level
0…15 A dc
High
Current
Level
0…30 A dc
Содержание 1407-CGCM-DLR
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM DLR User Manual OriginalInstructions...
Страница 14: ...14 Rockwell Automation Publication 1407 UM002B EN P February 2019 Chapter 1 General Information Notes...
Страница 204: ...204 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix B CGCM DLR Unit Math Models Notes...
Страница 220: ...220 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix D Specifications Notes...
Страница 260: ...260 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix G Installing the Add on Profile Notes...
Страница 266: ...266 Rockwell Automation Publication 1407 UM002B EN P February 2019 Index Notes...
Страница 267: ......