PL-11

 User Guide   AP7590 issue 1 

 

 

 

Grounding the metal plate

   

Ensure 

the faceplate and any metal parts are correctly 
grounded to ensure operator safety.  The plate should 
be connected to a local safety ground, not the PL-Anet 
screen connection.  Use a ground wire or physical 
contact with a grounded back box. 

 

 

 

PL-Anet connection

     

RJ45 sockets are 

provided for the serial port IN and OUT connections.  
Use unbooted plugs to ensure the cables can fit into 
the backing box.  Allow enough cable service loop for 
removing the module from the backing box. 

 

 

 

 

 

 

 

 
Wiring standards

   

Use flame 

retardent CAT5 STP (shielded twisted 
pair) cable.  The connection follows 
the EIA/TIA 568B wiring colour 
scheme.  Ensure all ports and cables 
in the system are wired to this 
scheme.  The RJ45 connector wiring 
is shown here. 

 
End of chain termination

     

As with any 

RS485 system, the last 

PL

  device  needs  to  have  a 

terminating resistor fitted to its output port.  

PL-11

 

modules are supplied with a terminating RJ45 plug 
(Allen & Heath part number 003-082). 

 

 

 

 

 

 

 

 

Connection to the iDR

   

The PL-Anet network 

plugs into the 

iDR

 unit using an RJ45 connector.  This 

is wired to the 568B scheme.  The PL-Anet port 
provides the RS485 serial communication and +20V 
DC power to the chain of 

PL

 modules.   The device 

addresses are automatically allocated per type in the 
order they appear in the PL-Anet chain. 

  

Testing the wiring

   

Before powering 

up the system make sure all the wiring is inspected and 
continuity tested.  This is important as wiring errors 
may result in damage to the equipment. 

Powering up the PL system

   

Ensure that 

the 

iDR

 PL-Anet port is active.  Its green ‘active’ LED 

should  be  lit.    If  not,  use  the  iDR  System  Manager 
software Communications Option menu to activate the 
port.  Plug in the PL-Anet cable.  The iDR System 
Manager screen should display icons on the right hand 
toolbar for each PL device it recognises. 

 

Diagnostics

   

If a fault is suspected check the two 

diagnostics LEDs on the 

PL-11 

connector PCB.  Both 

the red and green LEDs should be lit once 
communication with the 

iDR

  is  established.    Also 

measure the PL-Anet +20V supply feed between the 
blue wires (+20V) and the brown wires (0V).  For 
reliable operation this voltage should not drop below 
+11V  with  all  PL  LED  displays  turned  on.    If  a  fault  is 
found, first check for correct wiring.  If further 
assistance is required contact Allen & Heath technical 
support. 

 

Programing the IR functions

   

Read user 

guide AP 5196 that comes with the 

PL-5

.  The functions 

are programmed using the iDR System Manager 
software.  For further details refer to the Help file that 
comes with the software.  Program the function for 
each 

PL-11

 wall plate in the system.  A simulation 

window is also provided for testing the system. 

 

 

 

 

 

 

 

Select the contol number for the button you want to 
program.  The buttons are numbered 1 to 14 as shown 
below.  Available functions for each button are: 

Level up/down (I/P, O/P, X/P) 
Group level up/down (I/P, O/P, XP) 
Mute toggle (I/P, O/P, XP) 
Polarity toggle (I/P, O/P) 
Monitor select (I/P, O/P) 
Preset recall 
MIDI message string  
 

 

OUT

FROM PREVIOUS PL DEVICE

100 ohms TERMINATOR

IN

PL-Anet

OUT

FROM PREVIOUS PL DEVICE

TO NEXT PL DEVICE

IN

OR TERMINATOR

1  WH/OR

2  OR

3  WH/GN

4  BL

5  WH/BL

6  GN

7  WH/BN

8  BN

5

4

3

2

1

PL-5

5

4

3

2

1

6

7

8

9

12

13

10

11

14