Attach wiring to terminal blocks on ALK board as shown.
Notes about Wiring:
The EI (external inhibit) option uses NO (normally open) dry access control contacts to inhibit the ALK.
Closing the access control contacts inhibits the ALK. When the access control contacts are re-opened, the ALK re-arms with no delay.
RX, LX, and EI inputs are not polarized.
OR
*
Yellow
Red
Blue
(Optional)
Von Duprin Power Supply
(PS902)
RX-LC Switch *
Insulate unused wire
(Optional)
EI
-
NO
(normally open
access control
dry contacts)
NC
C
NO
24 VDC
9V Battery
Connector
EPT-10 or
Electric Hinge
Violet
White
Gray
LX-LC Switch
Insulate unused
wire
GND
RX
GND
EXT IN
GND
24 VDC
S1
S2
GND
LX
The current draw of a Von Duprin exit alarm
ALK is .25 amp when alarm is activated.
6
Adjust alarm reset time, as needed.
Adjust dip switches as shown below to adjust reset time.
L
Auto Reset Time (minutes): Amount of time alarm will sound before resetting automatically (no manual intervention).
S2.2
S2.1
Reset
OFF
OFF
NONE
ON
OFF
1.5
OFF
ON
3
ON
ON
4.5