IF-4076-0 Access Manager
Controller
00-4076-04xx
Страница 1: ...IF 4076 0 Access Manager Controller 00 4076 04xx...
Страница 2: ...ng the access manager 11 4 Connecting the access manager 11 4 1 Cable routing 11 4 2 Wiring components 12 4 3 Connecting the controller 16 5 Initial operation 17 5 1 Connecting the controller to the n...
Страница 3: ...upporting plate for I O controller boards and power n n n n n supply unit Cable gland M20 x 1 5 Strain relief plates with screw nuts Split ferrite Accessory bag with screws screw anchors and a key for...
Страница 4: ...cautionary measures to ensure safe installation NOTICE Property damage due to transient overvoltages Transient overvoltages surges bursts in the energy supply network can lead to malfunctions and fail...
Страница 5: ...braiding 100 m From category 5 Cable to floating status contacts control cable 100 m J Y St Y 2 x 2 x 0 6 mm2 J Y St Y 2 x 2 x 0 8 mm2 RS485 bus cable to parent or child devices 1200 m J Y St Y 2 x 2...
Страница 6: ...control and monitoring n Storage of data required for offline operation e g credential numbers temporal and local permissions In offline mode the access manager takes over the functions of the host sy...
Страница 7: ...fuse 7 Transformer 8 Supporting plate for up to 16 I O controller boards The anti tamper switch 2 can be configured in such a way that it is monitored by the host system and triggers an alarm when th...
Страница 8: ...1 Interflex Datensysteme GmbH IF 4076 0 Access Manager 8 Components 3 6 7 5 8 1 4 2 1 Host system 2 IF 4070 controller 3 Slave Terminal 4 Readers 5 Control element 6 Door opening push button 7 Door co...
Страница 9: ...tery for emergency power supply IF 4070 only 7 Screw terminal for the connection of the power supply 8 RJ45 socket for the connection to the Ethernet network host system 9 USB connection for future us...
Страница 10: ...2 System overview 2021 Interflex Datensysteme GmbH IF 4076 0 Access Manager 10...
Страница 11: ...Connecting the access manager 4 1 Cable routing Observe the notes under Cable lengths and cable types 5 Recommended way to lay the cables to the housing n Power supply cable and protective earth Bott...
Страница 12: ...r edges with the enclosed grommets 2 3 Pierce a small hole in the grommet and feed the cable into the device 4 Secure all inserted cables using the shield connection terminals 4 5 Ground the cable shi...
Страница 13: ...ls max Bus 3 6 slave terminals max Make sure that each slave terminal has a unique hardware address within the bus Data cables with slave terminals can be connected in two ways Connections on the prin...
Страница 14: ...ers or signal lamps up to 30V 2A NO or NC contacts can be used for switching An NO or an NC contact can be used for switching devices up to 30 V 2 A Outgoing cables can be looped at the PAT terminals...
Страница 15: ...IN 7 11 IN 8 12 GND 14 GND 2 GND 4 GND 6 GND 8 GND 10 GND 12 GND Cable shield 10 Cable shield 13 or 14 Screw terminals for relays 800 801 802 Relay 1 Relay 2 Relay 3 Relay 4 Relay 5 Relay 6 Relay 7 Re...
Страница 16: ...res Therefore please note the following u Use shielded cables Cable lengths and cable types 5 u Ground the shields on the devices and cables u Provide power to actuators e g door openers separately fr...
Страница 17: ...0013 n Via service interface or USB Service interface USB IF 4xxx controller 75 4070 0001 service cable 4xxx connection in housing IF 4070 controller 75 4070 0002 service cable 4xxx connection via RJ...
Страница 18: ...tering a password are the network services started and the network connection can be established u Establish network connection After the power supply has been switched on the device executes the foll...
Страница 19: ...nput syntax for commands n Commands are written in lowercase n Options are separated from the command by a blank and the minus sign n lists all possible command options n Press the Enter key to confir...
Страница 20: ...tive 172 18 12 65 16 IPv4 gateway active 172 18 70 1 Port 2001 Hostname IF xxx fieldservice IF xxx The subnet mask is appended to the IP address as CIDR notation e g 172 18 70 23 16 CIDR notation Subn...
Страница 21: ...terminals only Protocol terminalbus 0 erfProt 1 rsiProt 9600 8 noParity Your license allows 16 terminals as maximum Description base address Base address max 16 No of term bus n Number of terminals o...
Страница 22: ...ware address with which the time access program manages slave terminals TNo Host management number The numbers are configured in the time recording access control program and are displayed after the d...
Страница 23: ...performs the following actions n Close application n Shut down operating system n Boot operating system n Restart application 1 Set switches 2 Shortly press the Reset button 3 Wait until the RUN LED...
Страница 24: ...k settings to factory default The network settings are reset 1 Set switches 2 Shortly press the Reset button The previous network settings are not saved temporarily unlike in earlier device variants F...
Страница 25: ...ter the system password 2 Adjust the paths for the programs pscp exe and plink exe if required for example if you have saved PuTTY on a USB stick 3 Start cmd exe and run the desired batch file A detai...
Страница 26: ...4 x 105 Weight Approx 8 5 kg Housing material Lacquered sheet steel Installation type Surface mounting with screws Humidity Max 95 non condensing Ambient temperature 4 C to 40 C Cable feed Surface mou...
Страница 27: ...m Ethernet as per IEEE 802 3 TCP IP Service interfaces Ethernet network connection with SSH Serial connection RS232 Interfaces to slave terminals 3 x RS485 Degree of protection IP30 Power supply via E...
Страница 28: ...curacy of the information provided which is subject to change or updates without prior notice The original manual is in German Other languages are translations of the original manual Version 09 21 Thi...