Operation
Algas-SDI Operation and Maintenance Manual - VH100-VH200
3-4
Manual Startup Guide
Startup combustion air supply.
Open gas shut-off valve and start ignition sequence.
Visually check for flame to confirm that burner has lit.
DANGER:
If no flame can be seen, close the gas valve to stop gas
flow. Allow flame safety to purge the body of gas before attempting to
restart the burner.
Manual Shutdown Guide
Close the gas shut-off valve at the burner.
Allow the air supply to run until the temperature of the
chamber is less than 1000 °F.
Shut off combustion air supply.