Installation
Algas-SDI Operation and Maintenance Manual - SH100-SH200
2-4
Checklist Before Installation
Intake
To allow use of fresh combustion air from outdoors, provide an
opening in the room of at least one square inch per 4,000 BTU/hr. In
the presence of corrosive fumes or materials in the surrounding
environment, supply burner with clear air from an uncontaminated
area or provide a filtering system which shall not impede burner
operation.
Exhaust
Do not allow exhaust to accumulate in the work area. Provide means
for exhausting them from the furnace and the building.
Access
Install the burner in such a way that you can get easy access for
inspection and maintenance.
Environment
Verify the local environment matches the operating specifications of
the burner. Check the following items:
Type and supply pressure of the fuel
Availability of enough fresh, clean combustion air
Humidity, altitude, and temperature of air
Absence of damaging corrosive fumes or materials in the air
Prevent direct exposure to water
Preparing the Burner
Several components must be installed on a burner before it can
operate. See installation instructions below.