Maintenance/Commissioning
Algas-SDI Operation and Maintenance Manual - SH100-SH200
4-2
Step 5: Stop Procedure
WARNING:
Do not turn the combustion air blower off until the
chamber temperature is below 250°F (121°C). This will prevent hot
gases from back flowing into the burner and blower causing damage
to the burner.
Stop the burner through the burner control system.
Run the combustion air blower until the chamber
temperature drop below 250°F (121°C).
Shut off the combustion air blower.
Close all manual gas valves to the burner.