16
Er08
Encoder error. Inability to adjust the number of revolutions
Er09
Water pressure too low
Er10
Water pressure too high
Er11
Error due to internal clock problem
Er12
Turning off due to unsuccessful ignition
Er15
Power outage longer than 50 minutes
Er16
Communication error RS485
Er17
Air flow controller error
Er18
Pellet shortage
Er25
Cleaning motor error
Er39
Air flow controller broke down
Er41
Minimum airflow in the CHECK UP phase has not achieved
Er42
Maximum air flow has been achieved
Er47
Auger encoder signal error
Er48
Error due to inability to adjust the number of revolutions of the auger motor
Er52
Module error I/O I2C
- Other messages:
Sound
If this message is shown in the Check Up Phase, it indicates that the temperature at one or more probes
is equal to the minimum value (0 ° C) or the maximum value (depends on the probe type). Ensure that
the probe is not open (0 ° C) or in short circuit (the maximum value on the temperature scale).
Service
This message informs you that the planned number of hours has been reached and that it is necessary
to call the maintenance staff.
Clean
This message informs you that the planned working hours have been reached and that it is necessary to
clean the boiler .
Block Ignition
This message occurs if the system shuts down while it is still in the ignition stage. The system will stop
only when it goes into the Run Mode.
Link Error
This message informs you that there is no communication between the LCD display and the controller in
the boiler .
Standby Man
This message appears if the system is in Standby Mode after the P5 key has been pressed.
- Visualisations:
By pressing the P4 and P6 keys you enter the visualisation menu. In this menu you can see the values of some system
parameters.
L3 On P1 Pump
Led number and state of the pump outlet
L4 Off Safety Valve
Led number and state of Aux 1 outlet
L5 Off Out not used
Led number and state of the outlet of the additional motor
L6 On Load Engine
Led number and state of Aux 2 outlet
L7 Off Out not used
Led number and state of Aux 3 outlet
Exhaust T.:103
Flue gases temperature (°C)
Water T.: 55
Water temperature (°C)
Buffer T.: 52
*Buffer temperature (°C)
Room T.: 21
*Room temperature (°C)
Pressure: 1548
*Water pressure in the boiler (mbar)
Air Flux: 680
Flow rate of primary air (cm/s)
Speed Fan: 1000
Speed /voltage of flue gas motor (rpm/V)
Auger ON: 800
Speed/voltage of auger motor (rpm/V)
Product Code 448-0000
System code
FSYD01000135.0.2
Controller firmware version
PSYSF01000209.0.2
Display firmware version
* If the boiler configuration has no installed probes, these values are not visible.
Menu
The menu contains the User Menu and the Technical Menu.
The Technical Menu contains the settings and features by which the manufacturer can modify the parameters and
configuration of the system. The Technical Menu is not available to the user, but only to the authorized representative of the
manufacturer.
User Menu
By pressing P3 key, you get into the User Menu