![Alfa Laval ThinkTop V50 Скачать руководство пользователя страница 13](http://html.mh-extra.com/html/alfa-laval/thinktop-v50/thinktop-v50_instruction-manual_2895002013.webp)
Terminals V70 Digital-IO 24V
1
Power supply
24V
(brown)
2
Power supply
GND
(blue)
3
out
Status OK
(white)
4
out
Valve de-energised (DE-EN)
(black)
5
out
Main valve energised (EN)
(grey)
6
out
Upper seat lift energised (USL)
(pink)
7
out
Lower seat push energised (LSP)
8
in
Solenoid valve 1 for main valve (SV1)
9
in
Solenoid valve 2 for USL (SV2)
10
in
Solenoid valve 3 for LSP (SV3)
1
Seat lift sensor
Supply
(brown)
2
Seat lift sensor
GND
(blue)
3
Seat lift sensor
Signal
(black)
M12 plug option wiring overview (8-pin A-coded plug)
Factory wiring overview for each solenoid valve configuration
1
4
8
6
2
7
5
3
2066-0049
Control board
1x3/2
2x3/2
3x3/2
1x5/2
Terminal reference
1
24V
Brown (pin 1)
Brown (pin 1)
Brown (pin 1)
Brown (pin 1)
2
GND
Blue (pin 3)
Blue (pin 3)
Blue (pin 3)
Blue (pin 3)
3
out: Status
White (pin 2)
White (pin 2)
White (pin 2)
White (pin 2)
4
out: DE-EN
Black (pin 4)
Black (pin 4)
Black (pin 4)
Black (pin 4)
5
out: EN, Main valve
Grey (pin 5)
Grey (pin 5)
Grey (pin 5)
Grey (pin 5)
6
out: USL, Upper seat
Pink (pin 6)
-
-
Pink (pin 6)
7
out: LSP, Lower seat
Violet (pin 7)
Violet (pin 7)
-
Violet (pin 7)
8
in: SV1, Main valve
Orange (pin 8)
Orange (pin 8)
Orange (pin 8)
Orange (pin 8)
9
in: SV2, Upper seat
-
Pink (pin 6)
Pink (pin 6)
-
10
in: SV3, Lower seat
-
-
Violet (pin 7)
-
200000549-1-EN-GB
13
Installation 3
EN
www.sks-online.com
www.sks-webshop.com
Содержание ThinkTop V50
Страница 4: ...www sks online com www sks webshop com ...
Страница 6: ...200000549 1 EN GB 6 1 EC Declaration of Conformity EN www sks online com www sks webshop com ...
Страница 8: ...200000549 1 EN GB 8 2 About ThinkTop EN www sks online com www sks webshop com ...
Страница 18: ...200000549 1 EN GB 18 3 Installation EN www sks online com www sks webshop com ...
Страница 24: ...200000549 1 EN GB 24 4 Setup EN www sks online com www sks webshop com ...