Installation Manual 5850-023
TE91K022-EN3
BADK 082012
Operator Control
Jog shuttle
PUSH: SW version
TURN: Select menu
PUSH: Config menu
TURN: Select option
Left: Decrease
Right: Increase
LCDisplay
999.9 mS/cm
139.9 °C
0.001 mS/cm
000.1 °C
Max. indication
Min. indication
The back-lit display indicates the conductivity in mS/cm and the
temperature in °C. The jog shuttle is used for simple configuration of
the measuring range(s) and the temperature coefficient(s) as well as
the temperature range.
Refer to the detailed description under “Configuring the Conductivity
Sensor”.
Configuring the Alfa Laval Conductivity Sensor
Jog-shuttle
Step
Subject
Range
Display
Turn
Push
Note
1
Power on
starting
...
2
Actual value
1
yyyyy mS
zzzzz °C
Push
3
SW version
Actual version
Push
4
Actual value
1
yyyyy mS
zzzzz °C
Right
5
Set Range 1
1
4...20 mA
Actual range, mS
Push
Note 1
6
1
4...20 mA
Set range, mS
Left/Right
Push to set
Left: Decrease
Right: Increase
7
1
4...20 mA
New range, mS
Right
8
1
1
Resolution
Actual Coefficient
Push
Note 2
9
1
Resolution
Set coefficient
Left/Right
Push to set
10
1
1
Resolution
New coefficient
Right
11
Set Range 2
2
4...20 mA
Actual range, mS
Push
Repeat steps 5...10 for ranges 2...4.
12
Set temperature
range
4...20 mA °C
Actual range
Push
13
Set temperature
range
4...20 mA °C
Select range
Left/right
Push to set
Note 3