INSTALLATION & OPERATIONS GUIDE | MICROSET 4
© Honeywell LT-MS4IOG Rev. 04 | Revised October 2015
34
Setting the MAC address and BACnet device instance (MS4-TH-MSTP only)
Set the MAC address and BACnet device instance on the display using the MAC/Device Instance
screens in field service mode. NOTE: There are no DIP switches on the Microset 4.
NOTE
Two-digit codes only used for Custom Codes settings. In Field Service Mode, display shows
MS/TP MAC, not Ad, BACNET DEV INSTANCE HIGH, not D0 and BACNETDEV INSTANCE
LOW, not D1.
To set the MAC address and BACnet device instance
1.
Enter Configuration mode.
2.
Select the Field Service Button.
3.
Press the
RIGHT
navigation arrow to get to the MAC selection screen.
4.
Press the
UP
/
DOWN
arrow until MAC Address desired is displayed.
5.
Press the
RIGHT
navigation arrow to accept your change and scroll to the BACNET Dev
Instance High Screen.
6.
Press the
UP
/
DOWN
arrow on the screen to adjust the High (thousands) setting for the Device
instance.
7.
Press the
RIGHT
navigation arrow to accept your change and scroll to the BACNET Dev
Instance Low Screen.
8.
Press the
UP
/
DOWN
arrow on the screen to adjust the Low (ones) setting for the Device
instance.
The up or down counting of values for MS/TP MAC or BACnet Device Instance automatically continues
when you maintain pressure on the arrow, and accelerates to allow making large changes more quickly.
You may also set the BACnet device instance using the BACtalk front-end, like you can with VLCs. See
the
VLC Installation and Operations Guide
(LTBT-TM-Gen4VLC-IOG) for more information.
Table 7
MAC/Device Instance Mode
DESCRIPTION
RANGE
MS/TP MAC Address
0-127
BACNET Dev Instance High
0-4,194
BACNET Dev Instance Low
0-999 (or 0-303 if Dev Instance High is at 4,194)