ALERTON GP-IO-332 Скачать руководство пользователя страница 2

© Honeywell 

    Page 2 - Printed in USA

LT-GP-II-01  Rev. A  

Wiring

Once the GP-IO-332 is mounted, connect the power.
 

Fig. 2  

Wiring diagram.

Connecting power

Connect the GP-IO-332 to 24VAC power from a UL 
Listed Class-2 24VAC transformer (not included). You 
can use the same transformer for the GP-HUB-100 and 
other associated controller(s) as long as the total load 
does not exceed 100VA and all devices are half-wave. 
The GP-IO-332 is a half-wave device.

CAUTION!

Half-wave devices and full-wave devices must not

use the same AC transformer. You must maintain wiring
polarity. Failure to do so can result in equipment damage.

ATTENTION!

Les dispositifs demi-onde et les dispositifs à

onde pleine ne doivent pas utiliser le même transformateur AC.
Le défaut de maintient de la polarité du câblage peut
endommager l'équipement.

USB Power

The GP-IO-332 can also be powered from a USB cable 
that provides 5VDC power. Some USB ports can supply 
sufficient power and some can not. Review the user 
documentation for the power source to determine 
whether the USB port supplies sufficient power.

DIP Switches

The GP-IO-332 has two banks of DIP switches. The first, 
6-position switch, sets the network address for the 
wireless network (must match GP-HUB-100). The 
second, 8-position switch, is used to set the Remote 
Device address (0-99) that the device will use when 
connecting to the Hub.

The RSSI LEDs also flash to indicate error conditions.

Fig. 3  

Locations of GP-IO-332 components.

XX

XX

XXX

XXXXXXX

GND

COM

24V

AC

MSTP-

POWER

MSTP+

XFMR

24VAC

O/P

FUSED AC 

SOURCE

PANEL GROUND

Table 1  

RSSI Error Conditions

Flash Pattern

Status

One red

No communication or the device has not 
joined the wireless network

One yellow and two 
green

Wireless network MAC address does not 
match device type

Two green

Multiple devices have identical wireless 
network MAC addresses

One red and one green Lost communication with GP-HUB-100. 

Working to re-establish connection.

One flashing red and 
two solid green

Device initialization in progress

BO LED

AC POWER
TERMINALS

USB 
TERMINALS

AI TERMINALS

BO TERMINALS AO TERMINALS