6

Attach power

Remove the service panel from the rear of the A/C unit. Attach the quick disconnect terminals from the Sentree power 
supply to unused L1 or L2 

1

/

4

″ tabs on the line side of the A/C unit’s contactor. Use the included alcohol wipe to clean 

the surface inside the electrical compartment. Peel the adhesive pad on the power supply and attach it to the clean 

surface. Clip the current sensor around either of the L1 or L2 mains cables from the house, making sure that the arrow 
on the inner surface of the sensor points toward the contactor. Check that the latch on the sensor is closed properly.

LK

LK

NOTE:

 CLASS 2 WIRING TO BE ROUTED SUCH THAT IT WILL NOT COME INTO CONTACT WITH LINE VOLTAGE WIRING

Содержание SENTREE

Страница 1: ...i SENTREE Installation Manual ALF 000008...

Страница 2: ......

Страница 3: ...SENTREE Installation Manual...

Страница 4: ...60 Hz Maximum power consumption 12W REPLACEABLE FUSE Fuse specifications UL Listed Supplemental Circuit Protection T 5 0 A H 600 VAC Replace with same type and fuse rating Example Bel Fuse Inc 0ADKC5...

Страница 5: ...o condenser units powered by 240 VAC single phase 60 Hz power and must use the 1 4 inch tabs on the line side of the condenser s contactor This Sentree device is intended for use on systems up to 600...

Страница 6: ...1 2 3 4...

Страница 7: ...d 1 Sentree main housing 2 Cable harness 3 Current sensor 4 Power supply fuse assembly 5 Pressure sensors 2 6 Installation manual 7 Cable bushing 8 Iso propyl alcohol wipe 9 Foam tape 3 10 Cable ties...

Страница 8: ...Installation...

Страница 9: ...1 Turn off the Power Switch the power to the air conditioner to the OFF position WARNING RISK OF ELECTRIC SHOCK CAN CAUSE INJURY OR DEATH DISCONNECT ALL REMOTE ELECTRIC POWER SUPPLIES BEFORE SERVICIN...

Страница 10: ...e pressure sensors onto the service ports Make sure the connectors on top of the sensors are horizontal to prevent water from collecting inside the sensor Replace the caps onto the servicing end of th...

Страница 11: ...he surface inside the electrical compartment Peel the adhesive pad on the power supply and attach it to the clean surface Clip the current sensor around either of the L1 or L2 mains cables from the ho...

Страница 12: ...harness into the electrical compartment Plug the power supply and current sensor into the connectors on the harness Attach the green ground clip from the harness to an exposed sheet metal edge in the...

Страница 13: ...pressure sensors Connect the red cable on the harness to the liquid line pressure sensor Connect the blue cable on the harness to the vapor line pressure sensor Arrange both pressure sensor cables in...

Страница 14: ...vapor line blue temperature sensors on the harness to their respective pipelines using the included cable ties then wrap with foam tape Attach the ambient black temperature sensor to a shaded locatio...

Страница 15: ...10 7 Mount the harness Attach the harness overmold to a secure location outside of the A C unit such as the A C support bracket or the vapor line A cable tie is provided...

Страница 16: ...unit Plug the primary cable from the harness into the Sentree main housing by pressing the connector in and twisting Mount the Sentree main housing to a secure vertical surface with appopriate screws...

Страница 17: ...d switch the power back to the ON position The indicator light on Sentree will flash red Monitor the light until it turns green up to 2 minutes indicating a good cellular signal has been achieved Sign...

Страница 18: ...Need help For additional help or in case of issue visit alertlabs com support or contact us at help alertlabs com...

Страница 19: ......

Страница 20: ......

Отзывы: