Intended use 

 

 

2.1 Operational constraints 

 

2.1.1 The transducer is not intended for operation in aggressive and explosive-hazard 

environments. 

2.1

 

2  The  transducer  must  not  be  affected  by  direct  heating  from  heat  source  which  have 

temperature  over  50

C.  The  transducer  should  be  placed  in  buildings  where  there  are  no  sharp 

temperature variations or high-strength sources of magnetic field. 

 

 

2.2

 

Preparation for use 

 

 

2.2.1

 

After receiving the package, make sure that the packing is not damaged. Then unpack the 

package and make sure that content of package is not damaged and every item is in place. List of items 
is presented in table 3.  

 

Table 3 

Name and nomenclature 

Quantity 

Transducer 

Current transducer E1842C. Passport 

Current transducer E1842C. Operation manual 

1* 

Individual package 

Latch 

1** 

* On a 
** Should be installed on case of transducer 

 

 

2.2.2

 

Check the information on a cover of the transducer for correspondence with required 

parameters. 

 

 

2.3

 

Use 

 

2.3.1

 

To provide safety, all operations on mounting and maintenance should be done with 

respect to rules of safe usage of electric systems in which transducers should be installed. 

2.3.2

 

Layout work at place of installation should be done according to Annex C. 

 

2.3.3

 

Installation of the transducer on plant 

2.3.3.1

 

When mounting the transducer 

on the rail

-

 

place latch on case of transducer (latch snap should be fixed to ledge on case); 

-

 

fix lower snaps of latch on edge of rail and then gently push at the case of transducer until it is 
fixed on rail. 

Mounting on rail can be done if rail is mounted to horizontal or vertical surface. 
When the rail is mounted on the vertical plane, its distortion from horizontal position should 

not exceed 15°. 

2.3.3.2

 

When mounting the transducer 

on the panel

Содержание E1842C

Страница 1: ...1 CURRENT TRANSDUCER E1842C Operation manual 49501860 3 0015 РЭ ...

Страница 2: ...ded use 7 2 1 Operational constraints 7 2 2 Preparation for use 7 2 3 Use 7 2 4 Operation in extreme conditions 8 3 Maintenance and repair 9 3 1 Safety 9 3 2 Order of maintenance 9 3 3 Troubleshooting data 9 3 4 Metrology monitoring 10 4 Storage 11 5 Transportation 11 Annex A Transducer Schematic 12 Annex B General Form of the Transducer 14 Annex С Variants of Transducer mounting 15 ...

Страница 3: ...9501860 02 Transducer is mounted on the rail TH 35 in accordance with ГОСТ Р МЭК 60715 2003 or immediately on the panel Transducer is hardware SSI product of the third order according to ГОСТ 12997 84 Protection of the transducer against environmental activity is ordinary Guard level IP00 ГОСТ 14254 96 IEC 529 89 Operating Environment Climatic affecting for C4 Group ГОСТ 12997 84 Ambient Air Tempe...

Страница 4: ...35 С 0 9 Input signal frequency 45 to 65 Hz 0 5 Strength of external magnetic field with frequency 45 65 Hz A m 400 А m 0 5 Load resistance 0 to 200 above 300 to 500 incl 0 25 1 2 5 Limits of error due to 5 harmonic distortion for 2 th 4 th 6 th 8 th harmonic 1 of the fiducial value for 3 th 5 th 7 th 9 th harmonic 2 of the fiducial value 1 2 6 Set up time of performance heating up time is 10 min ...

Страница 5: ... C 1 2 14 Electrical insulation resistance between case and output circuit is at least 100 M in standard conditions 20 M to 80 R H at 50 C 2 M to 95 R H at 35 C 1 2 15 Overall dimensions 70x80x77 mm 1 2 16 Weight 0 3 kg 1 2 17 Average mean time to failure 75000 hours 1 2 18 Average operation time 10 5 years 1 3 Construction 1 3 1 General form of Transducer is presented in Annex B 1 3 2 Transducer ...

Страница 6: ...ollowing information is marked on a cover of the transducer Name and type designation Manufacturer s mark Unit symbols of input and output signals Load resistance range Overvoltage category Module of intrinsic error Designation of numbers and polarity of output terminals Serial number two last digits describe year of manufacture 1 5 2 Sealing of the transducer is done with a bitumen mastic 1 accor...

Страница 7: ...ndividual package 1 Latch 1 On a Should be installed on case of transducer 2 2 2 Check the information on a cover of the transducer for correspondence with required parameters 2 3 Use 2 3 1 To provide safety all operations on mounting and maintenance should be done with respect to rules of safe usage of electric systems in which transducers should be installed 2 3 2 Layout work at place of install...

Страница 8: ...cessary to provide free space of at least 15 mm for first mounting of transducer 2 3 4 Put a main lead of measured circuit trough the hole of the transducer 2 3 5 Fix wires to output terminals with respect to polarity 2 3 6 Make sure that transducer input signal range is suitable for measuring current of the circuit 2 3 7 Turn on an input signal on the transducer 2 4 Operation in case of emergency...

Страница 9: ...age after inspection is done turn ON input signal 3 2 2 To unfix transducer from rail insert screwdriver in groove located at lower part of transducer case 3 3 Troubleshooting 3 3 1 Faults probable reasons and solutions are given in table 4 Table 4 Fault Probable reason solution There is no voltage at transformer winding Brake or short circuit of transformer winding Replace transformer No output s...

Страница 10: ...e transformer T1 25 V Capacitor С1 24 V Capacitor С2 22 V Capacitor С3 10 V 3 4 Metrology monitoring 3 4 1 To be sure that metrological characteristics are acceptable and are in accordance with metrological characteristics presented in this manual transducer should be calibrated every 2 years Calibration procedure should be done in accordance with document 49501860 3 0009 МП Преобразователь измери...

Страница 11: ...ressive gases and other harmful ad mixtures leading to corrosion should not exceed maximum tolerable value of content of corrosion active substances for atmosphere of type 1 according to ГОСТ 15150 69 5 Transportation 5 1 When packed in transportation package transducers can be transported on vehicle of any type In case of transportation on plane transducers should be placed in hermetic heated cha...

Страница 12: ...or RC 1206 130 Ом 5 YAGEO 1 Resistor R2 R3 Resistor RC 1206 1 2 кОм 5 YAGEO 2 Resistor T1 Transformer see table 1 Transformer according to table V1 Bridge rectifier MB4S FAIRCHILD 1 Bridge Rectifier V2 Zener diode 1 5SMC47A ON SEMICONDUCTOR 1 Zener diode V3 Zener diode SMAZ12 13 DIODES 1 Zener diode Designation Т1 Input AC range A 49501860 3 0015 49501860 5 0043 0 25 01 49501860 5 0043 01 0 50 02 ...

Страница 13: ...13 Annex B informative General Form of the Transducer Figure B 1 ...

Страница 14: ...14 Annex C informative Variants of Transducer Mounting Figure C 1 Mounting on the rail Figure C 2 Mounting on the panel ...