Alderon Industries ProbeX Series Скачать руководство пользователя страница 4

(Fig. 10)

(Fig. 11)

120 VAC Model 

ProbeX™ ONLY

230 VAC Model 

ProbeX™ ONLY

L1

120 VAC

Power

L1

N

Disconnect

L1

L1

N

L1 (Switched)

120 VAC

15 Amp

Detection

Circuit

M1

L1

L2

T1

T2

A1

A2

120V Coil

M1

Example Wiring

to 120V Pilot Circuit

Black

White

Red

L1

L1

L2

Disconnect

L1

L1

L2

L1 (Switched)

230 VAC

15 Amp

Detection

Circuit

M1

L1

L2

T1

T2

A1

A2

230V Coil

M1

Example Wiring

to 230V Pilot Circuit

Black

White/Red

Red

230 VAC

Power

1. After all the steps of the installation process have been completed, supply power to the pump switch and peform 

testing.

2. “Pump Down” Models - Raise the water level in the tank or monitoring area until the “stop” probe is submerged 

in water, the pump should not start. Continue raising the water level until the “start” probe is also submerged, the 

pump should start, and remain on until the water level recedes below the bottom of the “stop” probe. Repeat this 

process a couple of times to ensure the system is working properly.

3. “Pump Up” Models - Raise the water level in the tank or monitoring area until both the “stop” and “start” probes 

are submerged in water to start the test. Lower the water level until it recedes below the bottom of the “stop” probe, 

the pump should not start. Continue lowering the water level until the “start” probe is completely out of the water, the 

pump should start and remain on until the water level touches the bottom of the “stop” probe. Repeat this process 

a couple of times to ensure the system is working properly.

Testing the ProbeX™

The ProbeX™ uses an isolated patented circuit that detects water with no shock hazard at the probes.

1. Test system monthly to ensure pump switch and system integrity.

2. Keep both stainless steel probes clean and free of rust, mud, soap, or any type of non-conductive material by 

inspecting and cleaning monthly.

Maintenance

8. For hardwire models connecting to a pilot/control circuit, refer to the wiring schematics below for 120VAC circuits 

(Fig. 10) and 230VAC circuits (Fig. 11).

Installation of the ProbeX™ Continued

ProbeX

 Pump Switch | Model Nomenclature and Custom Part Number Chart 

(custom lengths available)

ProbeX™ (P)

Pump Down (D)

or

Pump Up (U)

120VAC (1)

230VAC (2)

Without Plug (WOP)

Piggyback Plug (WP)

Pump Switch

Cable Length

(feet)

Suspension Probe

Cable Length

(feet)

P

D

1WOP

15

S2

U

2WOP

20

S5

1WP

25

S10

2WP

30

S20

50

S30
S50

Select one item from each column above and enter selections in the Model Number Boxes 1-5 below, this is your ProbeX™ Pump Switch Custom Part Number.

MODEL # BOX 1

MODEL # BOX 2

MODEL # BOX3

MODEL # BOX 4

MODEL # BOX 5

P

Example Part Number: PD1WP20S30 | ProbeX™ Pump Switch, Pump Down, 120VAC Piggyback Plug, 20' Pump Switch Cable, and 30' Probe Cable

Alderon Industries  •  PO Box 827  Hawley, MN 56549  •  P: 218-483-3034  •  F: 218-483-3036  •  alderonind.com

Page 4 | Installation Instructions

ProbeX

 - Installation Instructions