Operation, Maintenance and Installation Manual 

Part Number - 8059

Pump Station Alarm

Schematic Drawing for Wiring

There are two (2) different ways to wire the alarm panel depending on which type of application being used, either 

Dry or Wet contacts from the main pump panel. The Pump Station Alarm Panel comes with a jumper wire installed 

on Terminals 3 and 4 (Fig. 1 and Fig. 3). If using a Dry Alarm Contact from the main pump panel, see Figure 2.

Outdoor Remote Alarm Panel

(Fig. 1)

(Fig. 2)

(Fig. 3)

Panel Features

Alarm LED 

Indicator

Alarm Silence 

Pushbutton

(auto reset)

(Cover Removed)

Buzzer

Auxiliary 

Contacts 

Relay

Silence

Relay

Field Connection

Terminal Block

Specifications

Primary Power

120 VAC from Main Control Panel Signal or 

Separate 120 VAC Feed

Input Signal

Dry Contacts Rated to 120 VAC, 

1 Amp Minimum

Wet Contacts Rated to 120 VAC

Auxiliary Contacts

Normally Open - Dry

120 VAC, 5 Amps Maximum

Enclosure

Type 4X Thermoplastic, Padlockable

Alarm Indicator

120 VAC, Red LED, 22mm Diameter

Alarm Buzzer

95db @ 2-feet