NOTE

:

 All wiring must conform to applicable local codes, ordinances, and regulations.

NOTE

Verify that all detector bases are installed, that the initiating-device circuits have

 

been tested, and that the wiring is correct.

- Wire the sensor base per the wiring diagram.
- Notify the proper authorities that the system is in operation.
- After all sensors have been installed, apply power to the control unit.
- Test the sensor(s) as described in the 

TESTING

 section of this manual.

- Install the sensor into the sensor base. Push the sensor into the base 
   while turning it clockwise to secure it in place.

NOTICE

This manual should be left with the owner/user of this equipment.

IMPORTANT

The detector must be tested and maintained regularly following 

NFPA 72

 

requirements. The detector should be cleaned at least once a year.

Weight:  

Diameter:

Height:

5.5 oz. (155 g)

4.0

˝

 (103 mm)

2.2

˝

 (55 mm) installed in Base

Operating Voltage Range: 

Standby Current: 

Maximum Alarm Current (LED on)  

Operating Humidity Range:    

Operating Temperature Range:

Adjustable Sensitivity:   

9 to 28VDC Volts Non-polarized 

 

60µA @ 24 VDC

30mA @ 24 VDC 

10% to 93% Relative Humidity,

14°F to 122°F (-10°C to50°C)

0.15

0.3dB/m

 

CONVENTIONAL FIRE ALARM SYSTEM

intelligent solutions 

intelligent solutions 

SPECIFICATIONS

INSTALLATION

BEFORE INSTALLING

INSTALLATION DIAGRAM

Remove power from initiating-device circuits before installing detectors