NOTE
:
All wiring must conform to applicable local codes, ordinances, and regulations.
NOTE
:
Verify that all detector bases are installed, that the initiating-device circuits have
been tested, and that the wiring is correct.
- Wire the sensor base per the wiring diagram.
- Notify the proper authorities that the system is in operation.
- After all sensors have been installed, apply power to the control unit.
- Test the sensor(s) as described in the
TESTING
section of this manual.
- Install the sensor into the sensor base. Push the sensor into the base
while turning it clockwise to secure it in place.
NOTICE
:
This manual should be left with the owner/user of this equipment.
IMPORTANT
:
The detector must be tested and maintained regularly following
NFPA 72
requirements. The detector should be cleaned at least once a year.
Weight:
Diameter:
Height:
5.5 oz. (155 g)
4.0
˝
(103 mm)
2.2
˝
(55 mm) installed in Base
Operating Voltage Range:
Standby Current:
Maximum Alarm Current (LED on)
Operating Humidity Range:
Operating Temperature Range:
Adjustable Sensitivity:
9 to 28VDC Volts Non-polarized
≤
60µA @ 24 VDC
≤
30mA @ 24 VDC
10% to 93% Relative Humidity,
14°F to 122°F (-10°C to50°C)
0.15
~
0.3dB/m
CONVENTIONAL FIRE ALARM SYSTEM
intelligent solutions
intelligent solutions
SPECIFICATIONS
INSTALLATION
BEFORE INSTALLING
INSTALLATION DIAGRAM
Remove power from initiating-device circuits before installing detectors
Содержание CFS-SD300 Series