If in an operational case (case B) a generic control valve V closes the
fl
ow rate in an emitter
and the regulated pressure is maintained constant (for example with a DPCV), the
fl
ow in
all the sections from 1 to k decreases by q
m,V,A
and the pressure drop decreases to:
The pressure drop in a section
i
in the design case
Δ
p
i,A
, can be expressed approximately
by an equivalent resistance R
i
:
When the water
fl
ow changes, the equivalent resistance remains constant. If the
fl
ow is
reduced by q
m,V,A ,
the variation of pressure in a generic sector is:
Section
Ri
Δ
p
i,B
kPa/(l/h)
2
E1
E2
E3
E4
E5
kPa
kPa
kPa
kPa
kPa
1
28.93*10
-6
3.70
3.88
5.19
5.12
4.91
2
19.09*10
-6
1.00
1.56
1.53
1.44
3
36.73*10
-6
0.91
0.88
0.78
4
40.62*10
-6
0.28
0.23
5
31.82*10
-6
0.00
Con.1
57.21*10
-6
Con.2
47.48*10
-6
Con.3
56.43*10
-6
Con.4
40.20*10
-6
Con.5
41.39*10
-6
∑Δ
p
i,B
3.70
4.88
7.66
7.81
7.36
If the control valve V is designed with a pressure drop
Δ
p
V,A
, its authority is:
Using a minimum authority that is introduced for control engineering reason (i.e. a
v
>0.3), it
is possible to check if the selected valves are suitable.
Emitter
E1
E2
E3
E4
E5
-
Section from 1 to
1
2
3
4
5
-
Connection pipe
Con.1
Con.2
Con.3
Con.4
Con.5
-
Δ
p
V,A
5.24
4.60
2.77
2.99
3.72
kPa
Δ
p
reg
16.78
kPa
Δ
p
bal
3.12
1.63
2.20
1.03
0.00
kPa
∑Δ
p
i,B
3.70
4.88
7.66
7.81
7.36
kPa
a
v
0.40
0.39
0.30
0.33
0.40
-