UXSM Harness Installation
4200-088
10-1
Revision 1.03
10.
UXSM Harness Installation
Depending on the type of installation and equipment ordered, the UXSM can be powered several
different ways. Each method will be described below.
10.1.
24/48VDC Battery Powered
This harness connection will permit the UXSM to be powered directly from the battery it is monitoring.
This capability is only allowed on units monitoring 24/48VDC batteries. The following is a list of parts
required to construct the power harness. These parts should be included within the installation kit
provided the system was ordered with the intention to power the module from the battery.
Part Number
Drawing/Picture
Description
6002-121
50’ black 12GA wire used in
construction of DC power harness
6002-037
50’ Red 12GA wire used in
construction of DC power harness
1100-433MPM
Fuse holder assemblies used in
construction of DC power harness
4301-004
1A Fuse used in construction of DC
power harness
2880-004
1/4” shrink tubing used in
construction of DC power harness
2140-022
4 Position connector used in
construction of DC power harness
Table 8 - 24/48VDC Power Cable Parts List
A positive (red) and negative (black) lead are required to be constructed. Each lead will consist of a fuse
holder assembly 1100-433MPM, some length of red and black wire, which terminates to a four pin
connector 2140-002.
To construct the cable, pre cut the appropriate length of red and black wire. Ensure to add additional
length for service loops as required. Attach the red wire to pin 1 and the black wire to pin 4 of the four
pin connector.