PSV 2435-12 manual 1629en
1.
INSTALLATION
EP S AP S OUT SA B SA B -SDT*
SDT
STA RT
KICK-
Alarmtech ViP
F3
N L
+BAT- VOUT COM
F2
F1
Power S upply
PSV-2435
F1: T2H250V
F2: F4H250V
F3: F6.3H250V
Battery recharg .
current = 0.5 A
-
+
Case fixing hole
Case fixing hole
Battery chamber for
2 sealed lead acid batteries
12 V/12 Ah
Case fixing hole
Case fixing hole
Power output 24 V
Tamper detector
I/O cables
Battery fuse:
6.3 A quick
Output fuse:
4 A quick
Mains fuse:
2 A slow
+
-
Tamper detector
Mains
cable entry
To display
panel
Case earthing point
To earting connector in lid
Mains
connector
Signalling outputs
PE
N
L
Power Unit PSV 2435
PSV 2435-12 power supply installation and start-up procedure:
Fix unit in destination place using 4 fixing holes
Place two sealed lead acid batteries 12 V/ 12 Ah in battery
chambers
Make internal connection in battery pack connecting left bat-
tery (-) with right battery (+)
Make connection between right battery (-) and battery con-
nector using black battery cable connected to BAT-
Make connection between left battery (+) and battery con-
nector using red battery cable connected to +BAT
Make appropriate connections between power output and
power receivers
Make required connections between signalling outputs of PSV
2435-12 unit and cooperating units (outputs EPS, APS, OUT,
SAB, input –SDT*)
The socket outlet delivering 230 VAC shall be installed near
the power supply unit and shall be easily accessible
Make sure that cable delivering 230 VAC to power supply is
disconnected from mains
Carry in cable delivering 230 VAC to the unit using separate
mains cable entry on the left side and connect it to 230 VAC
input of PSV 2435 power unit – make sure that PE cable is
connected to PE input
Switch on mains delivering energy to power supply - PSV
2435-12 unit will start automatically delivering power to the