background image

V.

Troubleshooting Guide

Fault Output

{

Form "C" Relay Contacts rated 1 Amp @
24VDC

{

Relay Contacts labeled in the non-operational
(fault) condition

{

Fail-safe; active until an actual fault condition.

Visual Indicators

1. AC Presence  LED1:

Green LED

2. System OK  LED2:

Green LED

Fault Conditions

{

"SYS OK" Green LED extinguishes on:

1. Low AC / No AC / Blown AC Fuse
2. Low / High Battery or Output
3. Blown Battery Fuse

VI

Troubleshooting Chart

Replace PC Board.

Defective board

5) No relay transfer on fault

Rewire battery set.

Incorrect battery
hook-up.

Remove primary power and batteries, then
replace fuse. CAUTION. Observe polarity.

Blown battery fuse.

4) No battery back-up

Measure xfmr secondary voltage. If not within
proper range, replace transformer.

Incorrect or defective
xfmr.

Rewire battery set.

Incorrect battery
hook-up.

Remove system load and batteries; check
system output voltage. If OK recheck system
requirements, and/or measure output current
draw with an ammeter.

The system load is
greater than the
supply capability.

Check battery condition and replace if needed.

Defective battery.

3) Incorrect output voltage

Check xfmr secondary voltage at PC board
"Low Voltage AC Connection". If voltage is not
present, replace xfmr.

Loss of transformer
(xfmr) power.

Remove primary power and batteries, then
replace fuse. CAUTION.

Blown AC fuse.

Check AC primary supply.

Loss of AC power.

2) Green "AC ON" LED is not
illuminated.

See Symptom 4.

Blown battery fuse.

See Symptom 3.

Low or High output.

See Symptom 2.

Low AC / No AC /
Blown AC fuse.

1) Green "SYS OK" LED is off.
Relay Contacts transfer to NC.

Correction Procedure

Possible Cause

Symptoms

            Power Support System

                      Installation Instructions

AlarmSaf

 

 

65A Industrial Way  Wilmington, MA USA 01887-3499  (978) 658-6717  FAX: (978) 658-8638  Web Site:  www.alarmsaf.com

52-009L
032697

12 Volt
Battery

12 Volt
Battery

12 Volt
Battery

12 Volt
Battery

+

+

+

+

-

-

-

-

24 Volt Configuration

12 Volt Configuration

Parallel Hook-Up

Series Hook-Up

+

+

-

-

BATTERY CONFIGURATIONS

For further assistance, please contact the AlarmSaf Technical Service Department.

Отзывы: