Alarm SAF PS5-BFS-12-UL Скачать руководство пользователя страница 2

IV.

Mechanical Drawing

15.38

1.16

0

9.94

1.81

0

13.56

4.34

1.94 TYP

15.00

9.06

3.00

KEY LOCK

11.00

0

2.12

V.

Hook-Up Diagram

VI.

Troubleshooting Guide

Fault Output
PS5-BFS Models: Current limited voltage output

v

12V system; short circuit current is 25mA max

v

24V system; short circuit current is 50mA max

v

For fault reporting in fire applications, use Relay
Module RBKS-124P or RBKS-124N: See
Section III.

v

RBKS-124N required to detect AC fault when
no batteries are connected.

PS5-B03 Models: Form "C" relay contacts

v

Contacts rated 1A @ 24VDC

v

Fail-safe; active until an actual fault condition.

Visual Indicators

1. AC Presence LED1:

Green LED

2. Fault LED3 (PS5-BFS):

Yellow LED

System OK LED3 (PS5-B03):

Green LED

3. LED2 (Red LED) serves no user function.
4. Fault Conditions

Flashing Yellow LED (PS5-BFS) or Green
LED extinguishes (PS5-B03) on:
*Low AC / No AC / Blown AC Fuse
*Low Battery
*Blown Battery Fuse

VII

Troubleshooting Chart

            Power Supply/Battery Chargers

                      Installation Instructions

AlarmSaf

 

w

 

65A Industrial Way 

w

 Wilmington, MA USA 01887-3499 

w

 (978) 658-6717 

w

 FAX: (978) 658-8638  Web Site:  www.alarmsaf.com

52-130Z

090897

 

For further assistance, please contact the AlarmSaf Technical Service Department.

Rewire battery set.

Incorrect battery
hook-up.

Remove primary power and batteries, then
replace fuse. CAUTION.

Blown battery fuse.

4) No battery back-up

Verify switch settings in Section III.

Incorrect switch
setting.

Measure xfmr secondary voltage. If not within
proper range, replace transformer.

Incorrect or defective
xfmr.

Rewire battery set.

Incorrect battery
hook-up.

Remove system load and batteries; check
system output voltage. If OK recheck system
requirements, and/or measure output current
draw with an ammeter.

The system load is
greater than the
supply capability.

Check battery condition and replace if needed.

Defective battery.

3) Incorrect output voltage

Check xfmr secondary voltage at PC board
"Low Voltage AC Connection". If voltage is not
present, replace xfmr.

Loss of transformer
(xfmr) power.

Remove primary power and batteries, then
replace fuse. CAUTION.

Blown AC fuse.

Check AC primary supply.

Loss of AC power.

2) Green "AC" LED is not
illuminated.

See Symptom 4.

Blown battery fuse.

See Symptom 3.

Low battery.

"Fault Output" reporting

See Symptom 2.

Low AC / No AC /
Blown AC fuse.

1) Yellow "Fault" LED is flashing;
or Green "Fault" LED is off. 

Correction Procedure

Possible Cause

Symptoms

AC FUSE  (AGC-10)

BATT FUSE  (AGC-10)