1
345 Bayview Avenue
Amityville, New York 11701
CALL TOLL FREE: 800-ALA-LOCK
(800) 252-5625
ELECTRONIC EXIT DOOR ALARMS
PADDLE ARM MODEL 265/265L
PUSH BAR MODEL 715
INSTALLATION AND OPERATION INSTRUCTIONS
GENERAL DESCRIPTION
Models 265, 265L (long arm) and 715 are non-handed,
delayed egress, electronic exit door locking systems. Arming
is accomplished by actuating the deadbolt using a 1
1
/
8
” rim
cylinder (not included). When armed, depressing the paddle
(Model 265) or push bar (Model 715) will release the
deadbolt and sound an immediate alarm, however the
deadlatch will prevent the door from opening until the 15-
second exit delay has expired. Provisions are made for
instant alarmed exit in the event of actual emergencies, such
as smoke, fire, power failure, etc., using auxiliary detection
equipment.
A standard 9V alkaline battery is provided. This battery must
be installed at all times for proper operation of the unit. An
LED on the Control Box indicates that the unit is armed.
SPECIFICATIONS
Power:
12Vac, 20VA Transformer; 9Vdc Alkaline Battery
(Alarm Standby)
Current:
775mA max.; Alarm Circuit, Battery Only (Ac
Failure): Standby, 20µA typ.; Alarm, 75mA typ.
Standby:
1 year typ.
Battery Life:
200 alarm sequences typ. or constant alarm for
7 hours typ.
Latch Release Time:
13-15 seconds
Auto Alarm Shutdown:
2 minutes typ.
Sound Pressure Level:
95dB measured at 10 ft.
Operating Temperature:
20 to 135°F (-7 to 57°C)
Finish:
US28 Aluminum or US312 Duronodic Powder Coat
Dimensions (hxwxd):
Lock: Model 265, 8½”x18”x3¼”;
Model 715, 8½”x33”x3¼”; Control Box: Model 265 or
Model 715, 5”x3½”x2”
Shipping Weight:
Model 265, 11½ lbs; Model 715, 13½ lbs.
FEATURES
•
15-second delayed egress
•
Meets NFPA101 Life Safety Code
•
Local smoke-detector input (easy key reset)
•
Selectable alarm: continuous or two-minute shutdown
•
Exterior key control (requires additional rim cylinder)
•
Audible low-battery indication
•
Visual armed indicator LED (on Control Box)
•
Piercing electronic siren (95dB at 10 feet)
•
Full 1” throw deadbolt with rotating steel inserts.
EQUIPMENT SUPPLIED
•
The following items are supplied with the product:
•
Lock Assembly, with 9V alkaline backup battery
•
Single-Door Keeper Assembly
•
Paddle-Arm Assembly (Model 265); or Push Bar
Assembly (Model 715)
•
Control Box Assembly
•
Model 271 Flexible Conduit, with covers (2)
•
Power Transformer
•
5-Conductor Cable (10 feet)
•
Self-Adhesive Warning Labels (Model 265, 1; Model
715, 2) required to comply with NFPA 101 Hardware
OPTIONAL EQUIPMENT
•
Available on special order: Option 88 Version - Remote
Interface and Alarm Indicator Relay
•
Rim Cylinder, Model CER or equivalent (required)
•
Surface Wiring Kit, Model SWK715
•
Smoke Detector, 2-Wire. (Recommended: System
Sensor 1400, 2400, 2400TH; or 1451, 2451, 2451TH
with B401B Base)
INSTALLATION
Preliminary Considerations
Important!
To comply with National Fire Protection
Association Standard NFPA101, this lock must be connected
to an approved supervised automatic fire-detection system or
sprinkler system that will automatically unlatch the lock
instantly in the event of an emergency. See Connection to
Remote Life-Safety Equipment.
Models 265 and 715 are designed for use on doors equipped
with door checks to ensure that the door closes completely
and automatically. The Lock Assembly is mounted on a
single left- or right-handed reverse steel door. (These
instructions include information for mounting Model 715 onto
a narrow-stile glass door). Mounting onto a solid door
P5708A 11/93
Fig. 1 Typical Installation, left-handed reverse door, inside view. If
snaking wires within door, see Note above.