APS-300 Instructions 

Page 6

 

500-33315_A 

 

 

Содержание APS-300 Series

Страница 1: ...LED s Quality Manufactured in the USA with a lifetime Warranty Outputs are Power Limited Provided in Standard Enclosure 14 x 8 5 x 3 5 Precise Battery Regulation for all sealed Lead Acid Battery s Bat...

Страница 2: ...ndicator is a green LED which is illuminated when AC is present AC Line Primary Fuse Fuse GMA 2 5mm x 20mm 2A 250VAC Replace this fuse only while the equipment is electrically disconnected from the br...

Страница 3: ...ropriate input of a UL Listed Burglar Alarm or Access control panel When DC Power is normal the negative output is an open circuit with the LED OFF When the DC output voltage drops to a point where th...

Страница 4: ...f 25 from Non power Limited circuits 4 Connect DC devices to the Output Terminals Observe polarity On the distribution boards Negative is identified with a or COM The Positive is identified with or HO...

Страница 5: ...battery capacity with either 12V or 24V batteries The minimum battery capacity is 4Ah and the practical limit is 24Ah UL evaluated with an 18Ah battery on the 12V configuration and 2 9Ah batteries on...

Страница 6: ...APS 300 Instructions Page 6 500 33315_A...

Страница 7: ...unit is triggered The transfer relay is rated at 15A 12v and 12A 24vdc Power LED s A red LED above each output indicates which output is ON Input Trigger EOL 2 Pos Terminal block Will accept 14 28awg...

Страница 8: ...Red LED Indicates AC DC or Reversed DC Input on PD4C Each output has a green status LED indictor Current Draw is 6ma max per LED Circuit Breaker Models with Rated Output 1 42 Amps or below are Power L...