39
3910832
Subject to changes in keeping with technical developments!
5.6.2 Electrical air heater
The electrical air heater is wired in one or several switching groups. Each switching group for three-phase power
has three connection terminals plus one terminal for grounding each switching group.
Devices with electrical air heaters require a separate mains connection for the electrical air heater.
This supply line must be fused by the customer.
Technical data for the electrical heating register:
Device
type
Voltage
Electrical
power
Num-
ber of
switching
groups
Distribu-
tion of the
switching
groups
Distribution
of the power
Distribu-
tion of the
current
Supply line
Protection type
Standard/V4 A
LH 140
3~400 V/50 Hz
4.00 kW
3
1/3 1/3 1/3
3 x 1,33 kW
3 x 1,9 A
4 G 1,5 mm
2
IP 40 / IP 54
8.00 kW
3
1/3 1/3 1/3
3 x 2,67 kW
3 x 3,8 A
4 G 1,5 mm
2
IP 40 / IP 54
10.00 kW
3
1/3 1/3 1/3
3 x 3,33 kW
3 x 4,8 A
4 G 1,5 mm
2
IP 40 / IP 54
LH 250
3~400 V/50 Hz
12.00 kW
3
1/3 1/3 1/3
3 x 4,0 kW
3 x 5,8 A
4 G 1,5 mm
2
IP 40 / IP 54
15.00 kW
3
1/3 1/3 1/3
3 x 5,0 kW
3 x 7,2 A
4 G 2,5 mm²
IP 40 / IP 54
20.00 kW
3
1/3 1/3 1/3
3 x 6,67 kW
3 x 9,6 A
4 G 2,5 mm²
IP 40 / IP 54
LH 400
3~400 V/50 Hz
20.00 kW
3
1/3 1/3 1/3
3 x 6,67 kW
3 x 9,6 A
4 G 2,5 mm²
IP 40 / IP 54
28.00 kW
3
1/3 1/3 1/3
3 x 9,33 kW
3 x 13,5 A 4 G 2,5 mm²
IP 40 / IP 54
35.00 kW
3
1/3 1/3 1/3
3 x 11,67 kW 3 x 16,8 A
4 G 4 mm²
IP 40 / IP 54
LH 650
3~400 V/50 Hz
30.00 kW
3
1/3 1/3 1/3
3 x 10,0 kW
3 x 14,4 A
4 G 4 mm²
IP 40 / IP 54
45.00 kW
3
1/3 1/3 1/3
3 x 15,0 kW
3 x 21,7 A
4 G 6 mm²
IP 40 / IP 54
55.00 kW
3
1/3 1/3 1/3
3 x 18,33 kW 3 x 26,5 A
4 G 6 mm²
IP 40 / IP 54
LH 1000
3~400 V/50 Hz
45.00 kW
3
1/3 1/3 1/3
3 x 15,0 kW
3 x 21,7 A
4 G 6 mm²
IP 40 / IP 54
60.00 kW
3
1/3 1/3 1/3
3 x 20,0 kW
3 x 28,9 A
4 G 10 mm²
IP 40 / IP 54
75.00 kW
3
1/3 1/3 1/3
3 x 25,0 kW
3 x 36,1 A
4 G 10 mm²
IP 40 / IP 54
"Assembly"