Installation
CAUTION
Improper installation
Improper installation can cause serious or minor injuries and damage the control
panel. Installation must be performed only by fully qualified personnel.
The device is designed in a plastic enclosure for panel mounting. For the dimension
drawings see Appendix A.
4.1
Requirements
Install the device in a cabinet with clean, dry and controlled environment. For fur-
ther details see 2.1.
The module is designed for natural convection cooling. It should be taken into ac-
count when choosing the installation site.
The seal contact surface must be clean and smooth, so that the protection IP54
can be provided.
The device can be placed at any angle.
4.2
Mounting
prepare the mounting cutout according to Fig. A.1
make sure that the device is provided with the mounting seal
fit the device into the cutout
insert the 4 fastening clips into the slots on the top and the bottom of the device
insert the screws and tighten them to fix the device
4.3
Wiring
DANGER
Dangerous voltage
Electric shock could kill or seriously injure.
All electrical connections must be performed by a fully qualified electrician.
Ensure that the mains voltage matches the voltage marked on the nameplate.
Ensure that the device is provided with its own power supply line and electric
fuse.
WARNING
Switch on the power supply only after wiring of the device has been completed.
The layout of the terminal blocks is shown in Fig. 4.1 and the terminal assign-
ments in Table 4.1.
Ensure that the device is provided with its own power supply line and electric fuse
I = 1 A.
Connect the power supply to the terminals L / N.
The inputs should be wired in accordance with Fig. 4.2...4.8.
The outputs should be wired in accordance with Fig. 4.9...4.17.
The maximum conductor cross-
section is 1.5 mm².
Disabled inputs (parameter „Sensor type“ = OFF) should be short-circuited ac-
cording to Fig. 4.7.
►
NOTICE
Signal cables should be routed separately or screened from the supply cables.
Only a shielded cable may be used for signal lines.