Akron STYLE 9015 Скачать руководство пользователя страница 4

SUGGESTED NOZZLE TIP SIZE

TYPICAL PUMPER TESTS* (GPM)

NET

NOZZLE

PITOT

PUMP

TIP

PRESSURE

PRESSURE

SIZE

PSI

GPM

500 GPM PUMPER

100% rated capacity

150

1

1

2

58

508

70% rated capacity

200

1

1

8

88

351

50% rated capacity

250

1

1

8

46

254

700 GPM PUMPER

100% rated capacity

150

1

3

4

68

750

70% rated capacity

200

1

1

2

62

525

50% rated capacity

250

1

1

8

100

374

1000 GPM PUMPER

100% rated capacity

150

2

71

1002

70% rated capacity

200

1

3

4

60

704

50% rated capacity

250

1

1

2

58

508

1250 GPM PUMPER

100% rated capacity

150

2

1

4

69

1251

70% rated capacity

200

2

55

882

50% rated capacity

250

1

1

2

90

633

1500 GPM PUMPER

100% rated capacity

150

2

1

4

100

1506

70% rated capacity

200

2

78

1050

50% rated capacity

250

1

3

4

68

750

1750 GPM PUMPER

100% rated capacity

150

2

2 lines

55

882 ea.

100% rated capacity

150

1

3

4

” 

2 lines

94

881 ea.

70% rated capacity

200

2

1

4

66

1224

50% rated capacity

250

2

55

882

2000 GPM PUMPER

100% rated capacity

150

2

2 lines

71

1002 ea.

70% rated capacity

200

1

3

4

” 

2 lines

60

704 ea.

70% rated capacity

200

2

1

4

87

1402

50% rated capacity

250

2

71

1002

* Based on Test Requirements “UL 822 Certification of Fire Department Pumpers”

Underwriters Laboratories, Inc., Northbrook, IL.

Figures represented on the Discharge Table are accurate to ±3% at tested values in
accordance with the classification scope.

SUGGESTED NOZZLE TIP SIZE

TYPICAL PUMPER TESTS* (LPM)

NET

NOZZLE

PITOT

PUMP

TIP

PRESSURE

PRESSURE

SIZE-MM

kPa

LPM

2000 LPM PUMPER

100% rated capacity

1000

38.1

440

2018

70% rated capacity

1350

28.5

680

1401

50% rated capacity

1700

28.5

350

1003

3000 LPM PUMPER

100% rated capacity

1000

50.8

320

3051

70% rated capacity

1350

38.1

480

2112

50% rated capacity

1700

28.5

790

1518

4000 LPM PUMPER

100% rated capacity

1000

50.8

550

4024

70% rated capacity

1350

44.5

470

2839

50% rated capacity

1700

38.1

440

2018

5000 LPM PUMPER

100% rated capacity

1000

57.2

540

5035

70% rated capacity

1350

50.8

430

3543

50% rated capacity

1700

38.1

690

2525

6000 LPM PUMPER

100% rated capacity

1000

57.2

790

6113

70% rated capacity

1350

50.8

610

4221

50% rated capacity

1700

44.5

540

3040

7000 LPM PUMPER

100% rated capacity

1000

50.8 2 lines

430

3543

100% rated capacity

1350

44.5 2 lines

730

3528

70% rated capacity

1350

57.2

510

4906

50% rated capacity

1700

50.8

430

3543

8000 LPM PUMPER

100% rated capacity

1000

50.8 2 lines

550

4024

70% rated capacity

1350

44.5 2 lines

730

3528

70% rated capacity

1350

57.2

680

5644

50% rated capacity

1700

50.8

550

4024

* Based on Test Requirements “ULC-822 Guide for Listing and Labeling of

Fire Department Pumpers” Underwriters Laboratories of Canada, Scarborough,
Ontario, Canada

Figures represented on the Discharge Table are accurate to ±3% at tested values in
accordance with the classification scope.

Page 4

Page 5

Содержание STYLE 9015

Страница 1: ...tepped on 704607 Premier Farnell Corporation 2000 All rights reserved No portion of this can be reproduced without the express written consent of Premier Farnell Corporation PHONE 330 264 5678 or 800 228 1161 I FAX 330 264 2944 or 800 531 7335 I www akronbrass com Available in Canada through AKRON MANUFACTURING COMPANY PHONE 519 773 8431 I FAX 519 773 3794 WARRANTY AND DISCLAIMER We warrant Akron ...

Страница 2: ...ip replaces the hydrant outlet as the orifice 8 After use open bleeder valve and drain any water in the pitot air chamber Draining is especially important in freezing weather NOTE When ordering replacement tips check retaining ring 17 and O Ring 19 For other threads order by description and thread size ODM and TPI or by Akron Thread Code Package of 50 Ball Bearings P N 109041 Parts included in Pit...

Страница 3: ...pitot gauge against a test gauge regularly REPAIR PROBLEM ACTION 1 Pitot blade or tip damaged 1 Replace Instructions and align ment fixture provided with replacement blades 2 Leak around lock ring 2 Replace tip O Ring 3 Leak thru bleeder valve 3 Replace O Ring 4 No reading on pressure 4 Check for obstruction in gauge Pitot Blade waterway Clean coupling and gauge stem Replace gauge if necessary Pag...

Страница 4: ...cordance with the classification scope SUGGESTED NOZZLE TIP SIZE TYPICAL PUMPER TESTS LPM NET NOZZLE PITOT PUMP TIP PRESSURE PRESSURE SIZE MM kPa LPM 2000 LPM PUMPER 100 rated capacity 1000 38 1 440 2018 70 rated capacity 1350 28 5 680 1401 50 rated capacity 1700 28 5 350 1003 3000 LPM PUMPER 100 rated capacity 1000 50 8 320 3051 70 rated capacity 1350 38 1 480 2112 50 rated capacity 1700 28 5 790...

Отзывы: