If you select entries NTC, Pt100, Pt1000 or 4-20 mA, when you conclude the configuration process the wizard will
continue configuring the alarms
Configuration of input 1 is complete.
The wizard will proceed to the next input, repeating the same steps, until they are all configured.
Upon completion, the logger will automatically begin to record data.
IMPORTANT:
If you select NO, all entries will be left with default settings and the unit will begin to
record data. The entries may be re-configured later through the programming menu (see user manual).
Operation
Display modes
There are four possible modes for displaying instantaneous input readings. Press
P
or
O
to toggle between the
various modes:
Input reading
Alarm
status*
R
Alarm activated
(
Alarm signal activated
>
Alarm signal muted/disabled
T
Alarm/event delayed
<
Maximum alarm / Digital input activation (event)
=
Minimum alarm
Input disabled
Description
of the input
Input No.
Probe failure
Input reading
Input disabled
Individual input information
List of inputs
Summary of inputs
(only AKO-15740 and AKO-15742)
Sequential input information
*
Alarm status
4-
Activate minimum alarm?
5-
Minimum alarm temperature
6-
Minimum alarm delay time
2-
Maximum alarm temperature
1-
Activate maximum alarm?
3-
Maximum alarm delay time
Input
reading
Description
of the input
Input
reading
Description
of the input
20