Technical specifications

Power supply ...........................................................................................................................................85 - 264  V ~ / 47 - 63 Hz
Maximum consumption .......................................................................................................................................................10 VA
Communications: ..............................................................................................................................WIFI (802.11 b/g/n, 2.4 GHz)   
 

...................................................................................................................................Ethernet Port 10/100 Mbps

 

........................................................................................................................................................RS 485 9600

 

...............................................................................................Quad-band GSM/GPRS (850/900/1800/1900 MHz)

Relays...................................................................................................................8 relay outputs SPST, 30 Vac/Vdc, 1 A, cos 

j

=1 

Antenna ..........................................................................................................................................................................External
Working ambient temperature........................................................................................................................................0 to 40 ºC
Range of moisture permitted   ..........................................................................................................................................5 - 95 %
Maximum working height .................................................................................................................................................2000 m
Casing...........................................................................................................................Self-extinguishing UL94 V0 polycarbonate
Protection degree..................................................................................................................................................................IP20
Fixing.....................................................................................................................................................................DIN rail 46277

2

Connections ..........................................................................................................................Plug-in terminals, maximum 1.5 mm
Electrical and safety features .........................................................................................Double insulation (fitted), protection class II
Dimensions (with terminals and antenna fitted).....................................................................105 mm (W) x 135 mm (H) x 50 mm (D )

Simplified declaration of conformity

AKO Electromecánica S.A.L. hereby declares that the radioelectric device types 

AKO-5041

 (Akonet.Edge) conform to the provisions 

set forth by Directive 2014/53/EU.
The full text of the EU conformity declaration is available at the following internet address:

http://help.ako.com/manuales/declaracion-ue-de-conformidad

Start-up

1.-Access 

 (you must be registered).

akonet.cloud

2.-Access the “Edges” (A) section and click “+” (Activate new Edge) (B).

3.-Enter the data that appears on the label of the new AKONet.Edge (Serial no. and validation code) or click 

 and scan the QR 

code provided on the label.

4.-Finish the activation by filling in the requested data.
5.-After registering start searching for devices connected to the AKO Edge and activate them.
6.-From then on, the AKO Edge starts to transmit data to 

. For further information, please refer to the manuals available 

akonet.cloud

on our website.

Display and analysis of the logged data

Both the display of the logged data and the device configuration must be done in the 

portal.

akonet.cloud 

The portal also allows you to analyse the stored data using graphs, statistics and operating indicators. For more information visit  

akonet.cloud.

Wiring

Always disconnect the power supply to do the wiring.
For  disconnection,  the  power  supply  circuit  must  be  equipped  with  at  least  a  2 A,  230 V  switch,  located  near  the 

device. The power supply cable shall be of the H05VV-F or NYM 1x16/3 type. The section to be used will depend on current 
local  regulations  but  should  never  be  less  than  1.5  mm .   The  120  /  230 V~  wiring  area  must  be  kept  clear  of  any  other 

2

external element.

www.akonet.cloud

Add device

1

2

A

B

3

4

5

Tr+

Tr+

GND

GND

Tr-

Tr-

Tr- 

Tr- 

Tr- 

Tr- 

Tr+ 

Tr+ 

Tr+ 

Tr+ 

Gnd

Gnd

Gnd

Gnd

AKOGAS

AKOGAS

AKOGAS

AKOGAS

Terminating resistors are not required.

RS485

(MODBUS)

85 - 264 V~

/ 47 - 63 Hz

V1

V2

V3

N

Tr- 

Tr+ 

Gnd

C1

C2

C3

C4

R1

R2

R3

R4

C8

C7

C6

C5

R8

R7

R6

R5