
Keyboard
Installation instructions
1461H032 Ed.01
3
5
1
4
6
1
0
3
2 R
EV
.0
0 2
0
1
4
AKO ELECTROMECÁNICA
, S.A.L.
Avda.
Roquetes, 30-38
08812
•
Sant Pere de Ribes.
Barcelona
•
Spain.
Tel.: +34 902 333 145
Fax: +34 938 934 054
www.ako.com
We
reserve the
right to
supply materials
which may
be slightly
different from
those
described in
our Data
Sheets. Updated
information on
our web
site.
60
41,5
94
125,5
35
ø max. 3,7
171
1
Installation
Wiring
Display
ECO mode ON
Program Mode
Stand-by mode ON
Fast Freezing mode ON
FAN relay ON
DEF relay ON
Light ON /
2
RES relay ON
AUX relay ON
SET
SET
SET
SET
SET
Press for 5 seconds, allows changing the set point (SP). (Not available in thermometers)
Pressing for 10 seconds goes to the programming menu.
In the programming menu, go to the level displayed or accept the new value while setting a parameter.
Pressing for 5 seconds starts/stops defrosting. (Not available in thermometers)
The programming menu, allows you to scroll through the various levels or, during the setting of a parameter, to change the value.
Press for 5 seconds to start/stop Fast Freezing mode (rapid cooling). (Function available depending on the model).
The programming menu, allows you to scroll through the various levels or, during the setting of a parameter, to change the value.
Pressing for 5 seconds activates Standby mode, pressing for 2 seconds returns the equipment to normal mode. In Standby
mode, the equipment performs no actions and only the indicator is displayed on the screen
m
.
In the programming menu, go to the level displayed.
Pressing it for 1 second, activates or deactivates the cold room light (if P6=3). This function stays active although the unit is
in the stand-by mode. (Function available depending on the model).
In the programming menu, exit without saving parameter, return to previous level or exit programming.
Operation
16 A
16 A
16 A
16 A
6 A
8 A
8 A
S3 / DI2
S3 / DI2
DI1
DI1
S2
S2
S1
S1
1
2
3
4
5
6
7
8
9
10
1
1
12
13
1
2
3
4
5
6
7
8
9
10
1
1
12
13
14
15
AKO-D1464x
AKO-D1463x
I max.:
16 A
I max.:
16 A
L
N
L
N
COOL
COOL
AUX.
AUX
FAN
FAN
DEF
DEF
AUX.
The probe and its cable should
NEVER
be
installed in the same conduit as power,
control or supply cables.
Start-up
AKO-D1461x / AKO-D1462x
On power-up, the equipment will start up in Wizard mode (InI / 1
flashing), press
N
or
Q
to select the most appropriate
application and press
SET
.
1
: Chilling
2
: AC
3
: Heat/Incubators
The wizard will configure the parameters of the equipment for the
chosen application (see table).
AKO-D1463x / AKO-D1464x
On power-up, the equipment will start up in Wizard mode (InI / 1
flashing), press
N
or
Q
to select the most appropriate application
and press
SET
.
1
: Chilling
2
: Frozen
3
: Fruits and vegetables
4
: Fresh fish
5
: Soft Drinks
6
: Bottle racks
7
: AC
The wizard will configure the parameters of the equipment for the
chosen application (see table).
WARNING:
The default parameters by type of
application have been defined for the most common
applications. Check that these parameters are suitable
for your installation.
WIZARD
SP
d0
d1
F0
F3
InI=1: Chilling
2
4
20
8
1
InI=2: Frozen
-18
4
20
0
0
InI=3: Fruits and Vegetables
10
4
20
30
1
InI=4: Fresh fish
0
4
20
8
1
InI=5: Soft Drinks
3
24
20
8
1
InI=6: Bottle racks
12
24
20
30
1
InI=7: AC
21
96
0
99
1
AKO-D14631:
120 V~ +8% -12%
50 / 60 Hz
AKO-D14632:
230 V~ ±10%
50 / 60 Hz
AKO-D14632-C:
90-240 V~
50 / 60 Hz
AKO-D14641:
120 V~ +8% -12%
50 / 60 Hz
AKO-D14642:
230 V~ ±10%
50 / 60 Hz
AKO-D14642-C:
90-240 V~
50 / 60 Hz
Tr +
Tr +
Tr -
Tr -
G
n
d
G
n
d
Modbus*
Modbus*
1
1
2
2
3
3
* Depending on model
2
2
2
3
4
COOL relay ON
1
1
:In
AKO-D1461x / D1462x,
if P0=0
2
:In
AKO-D1461x / D1462x,
if P0=1
AKO-D1460x
AKO-D1461x
AKO-D1462x
AKO-D1463x
AKO-D1464x
AKO-D146xx-C
16 A
S1
S1
2
1
3
4
5
6
7
AKO-D1461x
AKO-D1461x
AKO-D14610:
230 V~ ±10%
50 / 60 Hz
AKO-D14612:
120 V~ +8% -12%
50 / 60 Hz
AKO-D14610:
230 V~ ±10%
50 / 60 Hz
AKO-D14612:
120 V~ +8% -12%
50 / 60 Hz
AKO-D14601:
120 V~ +8% -12%
50 / 60 Hz
AKO-D14602:
230 V~ ±10%
50 / 60 Hz
AKO-D14621:
120 V~ +8% -12%
50 / 60 Hz
AKO-D14622:
230 V~ ±10%
50 / 60 Hz
AKO-D14622-C:
90-240 V~
50 / 60 Hz
AKO-D14621:
120 V~ +8% -12%
50 / 60 Hz
AKO-D14622:
230 V~ ±10%
50 / 60 Hz
AKO-D14622-C:
90-240 V~
50 / 60 Hz
S1
2
1
3
4
5
6
AKO-D1460x
I max.:
16 A
I max.:
16 A
L
N
L
N
COOL
RES
16 A
16 A
Tr +
Tr +
Tr -
Tr -
G
n
d
G
n
d
Modbus*
Modbus*
6 A
6 A
DI2
DI2
DI1
DI1
S1
S1
1
1
2
2
3
3
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
13
13
14
14
15
15
AKO-D1462x
AKO-D1462x
I max.:
16 A
I max.:
16 A
L
N
L
N
COOL
ALARM
ALARM
RES
15
16
17
18
19
GSM ALARM
AKO-52042
15
16
17
18
19
GSM ALARM
AKO-52042
Mode: COLD
(P0=0)
Mode: COLD
(P0=0)
Mode: HEAT
(P0=1)
WIZARD
SP
d0
d1
P0
InI=1: Chilling
0
6
20
0
InI=2: AC
21
0
0
0
InI=3: Heat/Incubators
37
-
-
1
16 A
2
1
3
4
5
6
7
Mode: HEAT
(P0=1)
Warnings
-Using the equipment without following the manufacturer's instructions may affect the device's safety requirements. To ensure that the
device operates correctly, only probes supplied by AKO should be used.
-The unit must be installed in a location protected from vibrations, water and corrosive gases, where the ambient temperature does not
exceed that shown in the technical data.
-To ensure a correct reading, the probe must be situated in a location without any external heat influences except for the temperature which
is being measured or controlled.
-The power supply circuit must be provided with a main switch rated at at least 2 A, 230 V, located close to the equipment. The cables will
enter through the back and should be type H05VV-F or H05V-K.
2
-The gauge will depend on local regulations, but should in no case be less than 1 mm .
2
-Connecting wires for the relay contacts should be sized 2.5 mm .
-Between -40 ºC and +20 ºC, if the probe NTC is prolonged till 1.000 m with a mínimum of cable 0,5 mm², the maximum deviation will be of
0,25 ºC (extension cable for probe ref.
AKO-15586
)
NOTE:
Equipment not compatible with
AKO-14917
(external communication module) and
AKO-14918
(programming key)
GB
AUX Relay
Function as per
parameter P6
S1:
Probe 1, temperature in the chamber or cabinet.
S2:
Probe 2, defrost.
S3:
Probe 3, temperature of product / 2nd defrost.
DI1/DI2:
Digital Input 1 / Digital Input 2.
User Manual available on
http://www.ak
o.com/w4pu/page/qr/?qrcode=AK
ODOC0051