5532H301 Ed.02
Wiring
The wiring between the detector/button and the station should
NEVER
be installed in a conduit together with power,
control or feeder cables.
Always disconnect the power supply to do the wiring.
The power supply circuit should be equipped with a switch for its disconnection of at least 2 A, 230 V,
situated near the appliance. The power supply cable will be H05VV-F or NYM-1x16/3. The section to be
2
used will depend on current local regulations, but should never be less than 1.5 mm .
Cables for wiring the relay contact should have an adequate section depending on the unit to be connected.
The 120 / 230 V~ wiring must be kept clear of any other external element.
Make sure you have connected the batteries before starting-up the unit.
Pursuant to
RD 138/2011 IF12
(SP) and standard
EN-378-1
(EU), the Alarm's power supply must come from a
different circuit than the one used for the cooling and ventilation system.
15V
15V
Out
Out
AKO-55323
AKO-55326
AKO-55326
AKO-5512x
Alarm 2
(Only
AKO-55323B
, without battery)
5.- Configuration
Self-diagnosis function
The equipment includes a self-diagnosis system that informs the user in the event of a malfunction in the detector
or push-button or if there are errors in the wiring.
If a malfunction is detected, the alarm emits 3 short beeps every 2 minutes and the corresponding input indicator
flashes red.
Alarm 1
(With battery)
Tr+
Tr
-
Gnd
15V
In
Gnd
Alarm relay
Vac
Input
RS485
AKO-55123 / 55323:
230 V
~
± 10%
50 - 60 Hz
AKO-55120:
120 V~ + 8% - 12 %
50 - 60 Hz
C
NO
NC
Tr+
Tr
-
Gnd
15V
In
Gnd
Alarm relay
Vac
Input
RS485
230 V
~
± 10%
50 - 60 Hz
C
NO
NC
ALARM
ALARM
14