ºC
bar
ºC
bar
ºC
bar
PRG
5"
SET
Change value
Accept
changes
Enter
password*
Password
request
ºC
bar
ºC
bar
PRG
SET
Change
menu
Change
value
Level 1:
Menus
Level 2:
Parameters
Accept
changes
SET
Change
parameter
Level 3:
Values
ºC
bar
ºC
bar
ºC
bar
ºC
bar
IN PROGRAMMING
* The
TST
and
DSP
parameters are adjusted automatically when the expansion valve model
is selected. They should only be changed by qualified staff.
AKO
is not responsible for any
damage that may be inflicted on the installation.
For further information, refer to the user manual available on our
website:
www.ako.com
IMPORTANT:
In the event of an alarm or fault in any of the probes, the
controller closes the liquid solenoid and expansion valve until the problem is
solved.
Messages
*The default value of the password is 5. This may be changed using the
PSS
parameter.
Table of parameters
The equipment's operation functions are divided into 3 different groups.
The
Def.
column indicates the default parameters set in the factory. Temperature values are
expressed in ºC. (Equivalent temperature in ºF) and the pressure values in bar (equivalent
pressure in psi).
Adjustment of parameters
Using the programming menu, you will be able to configure the various parameters in order
to adapt the controller's operation to the needs of its installation.
In order to access the programming menu, press the
PRG
key for 5 seconds, or until the
message ''
PwD
'' is displayed. Using the
N
and
Q
keys enter the password (programmed
into the
PSS
parameter) and press
SET
. Once entered correctly, the password will not be
requested again for 30 minutes.
SET
5"
Press the
SET
button for 5 seconds to exit programming. If no key is pressed for 3
minutes, the controller will exit programming.
Level 1
Level 2
GROUP 1
Description
Values Min.
Def.
Max.
1.Pr
SH
Overheating set point
(K)
3.5
10
30
or
Initial opening for valve start up
(%)
0
50
100
ort
Duration of initial start up opening
(Sec.)
0
5
300
pro
Proportional gain
0.1
3
99.9
int
Integral time
(Sec.)
0
120
999
der
Derivative time
(Sec.)
0
30
999
lsM
Lower overheating alarm
0:
Deactivated
1:
Automatic reset
2:
Manual reset
0
1
2
lSS
Lower overheating alarm activation value
(K)
0.5
3
30
LSt
Lower overheating alarm turn-on delay time
(Sec.)
1
15
300
lsC
Lower overheating alarm deactivation time
(K)
1
3
30.5
MpM
Maximum pressure alarm in probe 2
0:
Deactivated
1:
Automatic reset
2:
Manual reset
0
1
2
Mps
Maximum pressure alarm activation value
(bar/psi)
-999
9
999
Mpt
Maximum pressure alarm turn-on delay time
(Min.)
1
1
15
MpC
Maximum pressure alarm deactivation time
(bar/psi)
-999
8
999
HSM
Maximum overheating alarm
0:
Deactivated
1:
Automatic reset
2:
Manual reset
0
0
2
HSS
Maximum overheating alarm activation value
(K)
10.0
30
40.0
HST
Maximum overheating alarm turn-on delay time
(Min.)
1
3
600
HSC
Maximum overheating alarm deactivation time
(K)
7.0
27
37.0
FPM
Freeze alarm
0:
Deactivated
1:
Automatic reset
2:
Manual reset
0
0
2
FPS
Maximum freeze alarm activation value
(ºC/ºF)
-100
0
200
FPT
Freeze alarm turn-on delay time
(Sec.)
5
30
200
FPC
Maximum freeze alarm deactivation time
(ºC/ºF)
-100
3
200
LPM
Lower pressure alarm in probe 2
0:
Deactivated
1:
Automatic reset
2:
Manual reset
0
0
2
LPS
Lower pressure alarm activation value
(bar/psi)
-999
0
999
LPT
Lower pressure alarm turn-on delay time
(Sec.)
5
5
200
LPC
Lower pressure alarm deactivation time
(bar/psi)
0
0.3
999
GROUP 2
Description
Values Min.
Def.
Max.
2.Pr
pu
Pressure units
0:
Bar
1:
Psi
0
0
1
Tu
Temperature units
0:
ºC
1:
ºF
0
0
1
EM
Selection of expansion valve model connected
1:
Danfoss ETS 12.5 / 25B
2:
Danfoss ETS 50B
3:
Danfoss ETS 100B
4:
Danfoss ETS 250
5:
Danfoss ETS 400
6:
Alco EX4
7:
Alco EX5
8:
Alco EX6
9:
Alco EX7
10:
Alco EX8 (330 s/s)
11:
Alco EX8 (500 s/s)
12:
Sporlan SEI 0.5~11
13:
Sporlan SEI 1.5~20
14:
Sporlan SEI 30
15:
Sporlan SEI 100
16:
Sporlan SEI 175
17:
Carel E2V
1
1
17
TST
Total steps for expansion valve*
0
262
999
DSP
Expansion valve speed*
0
250
999
GROUP 3
Description
Values Min.
Def.
Max.
3.Pr
pss
Parameter access password
0
5
999
rft
Type of refrigerant gas used:
0:
R-22
1:
R-134A
2:
R-404A
3:
R-407C
4:
R-410A
5:
R-717
6:
R-23
7:
R-507C
8:
R-HFO1234ze
9:
R-744
10:
R-407A
11:
R-407F
12:
R-507A
13:
R-245F
0
1
13
PSH
Pressure probe range (Maximum)
(bar/psi)
-999
15
999
PSL
Pressure probe range (Lower)
(bar/psi)
-999
-1
999
PSO
Pressure probe calibration (S2)
(bar/psi) -19.9
0
19.9
TSO
Pressure probe calibration (S1)
(ºC)
-19.9
0
19.9
JCR
Expansion valve opening speed limit
(%)
0.1
OFF
99.9
UrL
Maximum expansion valve opening limit
(%)
0
100
100
LrL
Lower expansion valve opening limit
(%)
0
0
100
Ft
Reading delay for probes (S1 and S2)
(Sec.)
0.1
1
10.0
COR
Lower expansion valve forced opening value
(%)
0.0
OFF
100
DM
Display mode:
0:
Displays options 1 to 4 sequentially
1:
Overheating value (ºK)
2:
Suction pressure value (Probe 2)
3:
Valve opening (%)
4:
Temperature value (Probe 1)
5:
Overheating set point
0
1
5
CID
Communication direction
1
1
128
CSP
Communication speed
(BPSx100)
48
96
384
INI
Initial settings (enter password and press
SET
)
0
0
999
Description
PS
Problem in the pressure sensor
TSD
Probe 1 not connected
TsC
Crossed temperature probe
MOP
Maximum Operation Pressure (MOP) alarm
LOP
Lower Operation Pressure (LOP) alarm
HS
Maximum overheating alarm
LS
Lower overheating alarm
FRA
Frost detection alarm
STP
Regulation stopped by external thermostat (ON/OFF Input)
CAL
Expansion valve initialisation
CLE
Valve closing underway due to fault in the electricity supply (emergency power
supply required)
EXPANSION
VALVE
LIQUID
SOLENOID
EVAPORADOR
PRG
SET
%
AKO-145601
AKO-D141xx
S1
S2
ºC
bar
SET
Technical specifications
Power supply .......................................................................24 V~ +10% / -15%, 50/60 Hz
Working ambient temperature ................................................-10 to 50 ºC, moisture <90 %
Storage ambient temperature .................................................-20 to 60 ºC, moisture <90 %
Relay solenoid valve ........................................................ (EN60730-1: 2(2) A 250 V~ SPST)
No. of relay operations..........................................................EN60730-1: 100.000 operations
Maximum voltage in the SELV circuits............................................................................20 V
Protection degree ...........................................................................................................IP2X
2
Connections ..................................Terminal to screw for cables with a section of up to 2.5 mm
Control device classification: Built-in assembly, with Type 1.B automatic operation action feature,
for use in clean situations, logical support (Software) class A and continuous operation. Degree of
contamination 2 acc. to UNE-EN 60730-1.
Double power input insulation, secondary circuit and relay output.
Rated pulse voltage ...................................................................................................2500 V
Pressure ball test temperature
Accessible parts..........................................................75 ºC
Parts that position active elements.............................125 ºC
Voltage and current declared by the EMC tests ........................................................207 V, 17 mA
Radio interference suppression test current ....................................................................270 mA