6-.Description of parameters and messages

The values in the 

Def.

 column are factory-set.

Thermometers parameters

Thermostats parameters

Functions and description

Values Min.

Def.

Max.

C0

Sensor calibration (Offset)

ºC

-20

0

20

C1

Sensor differential (Hysteresis)

ºC

1

2

20

C2

Set Point upper limit (It cannot be set above this value)

ºC

xx

99

99

C3

Set Point lowers limit (It cannot be set below this value )

ºC

-50

-50

xx

C4

Compressor protection delay type: 

0

=OFF/ON (From the last switch-off) 

1

=ON (At switch-on)

0

0

1

C5

Protection delay time (Value for the option selected in parameter C4)

min.

0

0

99

C7

Relay time in ON in case of faulty sensor (If C7=0 and C8

¹

0, the relay will always be OFF disconnected)

min.

0

10

99

C8

Relay time in OFF in case of faulty sensor (If C8=0 and C7

¹

0, the relay will always be ON connected)

min.

0

5

99

d0

Defrost frequency (elapsed time between 2 starts)

h.

0

1

99

d1

Defrost maximum duration

min.

0

0

99

d2

Type of message during defrost: 

0

=Current temperature display; 

1

=Defrost start temperature display; 

2

=Display 

dF

 message

0

2

2

d3

Message maximum duration (Time added at the end of defrost)

min.

0

5

99

L5

Access password to parameters

0

0

99

L6

Parameters transfer: 

0

=Disabled; 

1

=Send; 

2

=Receive

0

0

2

PU

Program version (Information)

P0

Type of operation: 

0

=Cold; 

1

=Heat

0

0

1

P1

Delay of all functions on power supply switch on

min.

0

0

99

P2

Allocation of password to Set Point: 

0

=Without allocation; 

1

=With allocation of L5 password

0

0

1

P3

Initial parameters: 

1

=YES, configure to “

Def

” and exit programming if P2=0)

0

0

1

P5

Address for units with communication (not activated)

0

0

99

P7

Temperature display mode: 

0

=Integers in ºC; 

2

=Integers in ºF 

0

0

2

EP

Exit programming

Messages

dF

It indicates defrosting is being carried out. In order to display “

dF

” during defrosting, it is essential that parameter d2 is set to option 2

E1

Sensor failure (Open circuit, crossed, temp.> 110ºC or temp.<-55ºC)

_ _

Temperature > 99 ºC/ ºF

EE

Memory failure

PA

Password request to enter in programming parameters or SET POINT

REMARK:

 When the time parameters are modified, the new values are applied once the current cycle is completed. In order for it to have an immediate effect, switch the controller off and 

then on again.

AKO-14918

Power supply

Programming

Transfer

7-.Parameters transfer

AKO-14918:

 Portable server without supply, to which can be copied by transferred the 

parameters programmed in a powered unit. The parameters may then be transferred again 
from the server to other identical powered units. To transfer parameters, other servers are 
available for controllers that should be programmed identically in high quantity without 
power supply.

8-.Relay operation and control

9-.Maintenance

10-.Warnings

Clean the controller surface with a soft cloth and soap and water. Do not use abrasive 
detergents, petrol, alcohol or solvents.

The  use  of  the  unit  different  to  the  manufacturer’s  instructions  voids  the  safety 
qualification.
To ensure correct operation of the apparatus, only NTC type probes supplied by 

AKO

 

should be used.
Between –40 ºC and +20 ºC, when the probe is extended up to 1.000 m with minimum 

2

0,5 mm   cable,  deviation  will  be  less  than  0.25  ºC  (probe  extension  cable  ref. 

AKO-15586

). 

TEMP.

SET

POINT

OFF

ON

C1

TEMP.

SET

POINT

OFF

ON

C1

Operation for COLD (P0=0)

Operation for HEAT

1301H201 Ed.03

GB