Small dimensions unit range, designed to monitoring, control and regulating refrigerating
generators (with manual or automatic defrost programmed by stopping the compressor) or
heating generators.

REMARK:

 A  reference  number  followed  by  /**,  one  or  two  alphanumeric  characters, 

means “with a special program”. In such a case, in addition to these general instructions, 
the particular instructions attached, with variations for each device should be followed. 

Temperature range: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -50 ºC to 99 ºC
Resolution, Set Point and differential: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 ºC
Input for NTC probe:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AKO-149XX
Controller accuracy: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 1 ºC
Probe tolerance at 25 ºC: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 0,4 ºC
Maximum input power: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 VA
Working ambient temperature:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 ºC to 40 ºC
Storage ambient temperature:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -30 ºC to 70 ºC
Voltage pulse assigned: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 800 V
Pressure ball test temperature

Accessible parts:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 ºC
Active elements positioning parts: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 ºC

CEM emission voltage test:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207 V
CEM emission current test: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 mA
Control  device  classification:  Independent  mounting,  with  characteristic  of  automatic 
operation action Type 1.B, to be used in clean situation, logical medium (software) class A.
Double insulation between the power supply, the secondary circuit and the relay output.

The controller must be installed in a place protected from vibrations, water and corrosive 
gases, and where the ambient temperature does not surpass the value specified in the 
technical data. 
In order the controllers be suitable having IP65 protection, the gasket should be installed 
properly between the apparatus and the perimeter of the panel cut-out where it is to be 
fitted. 
In order to give a correct reading, the probe has to be installed in a place without heat 
influences other than the temperature that is to be measured or controlled.

Fastening

To fix the unit, place the fasteners 1 over the sliders 2 as shown in 
the  figure.  Move  the  fasteners  in  the  direction  of  the  arrow.  By 

pressing tab 3 the fasteners may be moved in the opposite direction 
of the arrow.

Connection

See diagram in the unit rating plate. 
The probe and its lead should 

NEVER

 be 

installed  in  ducting  along  with  power, 
control or power supply wiring. 
The  power  supply  circuit  should  be 

connected with a minimum 2A, 230V, switch located close to the unit. The cables should be of 

2

2

the type H05VV-F 2x0,75 mm  or H05V-K 0,75 mm .

2

2

Section of connecting wires for relays contacts must be between 1,5 mm  and 2,5 mm . 

UP key

 

N

: When pressed for at least 5 seconds, a manual 

defrost  is  started  with  programmed  duration,  (in 
thermostats function).
In programming, it increases the displayed value.

DOWN key

 

Q

: In programming, it reduces the displayed 

value.

SET key:

 When pressed for at least 5 seconds, it displays 

the SET POINT temperature value, (in thermostats function).In programming, accept the 
programmed new value.

LED 1:

 Defrost in operation indicator. (in thermostats function).

LED 2:

 Relay ON indicator. (in thermostats function)

LED 2 flashing:

 Programming phase.

1-.Versions and references

2-.Technical data

3-.Installation

4-.Front panel functions

5-.Adjustment and configuration

5.2-.Parameters configuration

It should only be programmed or modified by personnel who are fully conversant with 
operation and possibilities of the equipment.

5.1-.Set Point temperature

The factory SET POINT default value is 0 ºC.
-Press 

SET

 key for at least 5 seconds to DISPLAY SET POINT. It displays the CURRENT SET 

POINT value and LED “

2

” start flashing.

-Press 

N

 or 

Q

 keys for CHANGE SET POINT to the required value.

-Press 

SET

  key  to  ACCEPT  THE  NEW  SET  POINT.  The  display  returns  to  the  current 

temperature display status and the LED “

2

” stop flashing.

When 

PA

 appears in display, PASSWORD programmed in L5 parameter should be enter for 

accede to the CURRENT SET POINT.
-Press 

SET

 key. 0 will be displayed to ENTER PASSWORD.

-Press 

N

 or 

Q

 keys to CHANGE NUMBER and DISPLAY PASSWORD.

-Press 

SET 

key to ACCEPT PASSWORD. The CURRENT SET POINT value will be displayed 

and possible to be modified.

Level 1 Parameters

-Press 

N

 + 

Q

 keys simultaneously for at least 10 seconds. The LED “

2

” will be flashing, we 

are in the LEVEL 1 PARAMETERS and in the display appear the first parameter “

C0

”.

-Press 

N

 key to access the next parameter and 

Q

 key to return to the previous one.

-Pressing  the 

SET

  key  in  the  last  parameter  EP,  the  controller  returns  to  the  current 

temperature display status and the LED “

2

” will stop flashing.

When 

PA

 appears in display, PASSWORD programmed in L5 parameter should be enter for 

accede to programming LEVEL 1 PARAMETERS.
-Press 

SET 

key. 

0

 will be displayed to ENTER PASSWORD.

-Press 

N

 or 

Q

 keys to CHANGE NUMBER and DISPLAY PASSWORD

-Press 

SET 

key to ACCEPT PASSWORD. The first parameter “

C0

” will be displayed.

Level 2 Values

-To DISPLAY CURRENT VALUE of any parameter, select the required one and press 

SET 

key. 

Once it is displayed, you can CHANGE VALUE pressing 

N

 or 

Q

 key.

-Press 

SET 

key  to  ACCEPT  THE  NEW  VALUE.  The  programming  returns  to  LEVEL  1 

PARAMETERS.

REMARK:

 If no key is pressed for 25 seconds in either of the previous steps, the controller 

will automatically return to the current temperature display status without modifying any 
of the parameters values.

Thermometers, thermostats and electronic controllers 
for 58 x 25,4 mm panel cut-out pattern

C

US

MODEL

FUNCTION

RELAY

POWER SUPPLY, 50/60 Hz

AKO-13012

Thermometer

-

12 V ~ ±20%

AKO-13020

Thermometer

-

120 V ~ +8% -12%

AKO-13023

Thermometer

-

230 V ~ ±10%

AKO-13112

Thermostat

16(4) A, 250 V, cos 

j

=1, SPST

12 V ~ ±20%

AKO-13120

Thermostat

16(4) A, 250 V, cos 

j

=1, SPST

120 V ~ +8% -12%

AKO-13123

Thermostat

16(4) A, 250 V, cos 

j

=1, SPST

230 V ~ ±10%

PANEL CUT-OUT

25,4

58

3

2

1

max.

18 mm

47,5

32

LED2 LED1

Down

key

Up

key

SET

key

5 Sec.

DISPLAY

SET POINT

CHANGE

NUMBER

If P2=0

ACCEPT

PASSWORD

CHANGE

SET POINT

ACCEPT

THE NEW

CURRENT

TEMPERATURE

CURRENT

SET POINT

ENTER

PASSWORD

DISPLAY

PASSWORD

PASSWORD

REQUEST

NEW SET

POINT

CURRENT

TEMPERATURE

PASSWORD

IF PROGRAMMED

LEVEL 1

PARAMETERS

LEVEL 2

VALUES

10 Sec.

DISPLAY

VALUE

EXIT

PROGRAMMING

CHANGE

NUMBER

If L5=0

PASSWORD

REQUEST

ENTER

PASSWORD

DISPLAY

PASSWORD

ACCEPT

PASSWORD

CHANGE

VALUE

CURRENT

VALUE

NEW

VALUE

ACCEPT

THE NEW

1301H201 Ed.03