Functions:
UP key
During programming, increases
the figure being displayed.
DOWN key
During programming, lowers
the figure being displayed.
+ Held down simultaneously for 10 seconds brings up the programming menu.
+ Held down simultaneously enters the new value.
Indicator LEDs:
LED 1
constant: Shows relay 1 is on.
flashing: Means relay 1 should be on according to the temperature detected by the probe,
but is not, owing to a programming condition.
LED 2
constant: Shows relay 2 is on.
flashing: Means relay 2 should be on according to the temperature detected by the probe,
but is not, owing to a programming condition.
LED PR
flashing: Programming set point or parameters.
The default (factory) setting for
SET POINTS 1 and 2 are 0ºC
- Hold the key down for 5 seconds. This opens the SP1 or SP2 setting menu (the PR led will flash).
- Press the
or
key to select SET POINT 1 or SET POINT 2.
- Press the
+
keys simultaneously to show the setting you want to change.
- Press the
or
keys to change the SET POINT to the figure you want.
- Press the
+
keys simultaneously to enter the new figure. When you do this, the display shows
the temperature again and the PR led stops flashing.
NOTE: If no key is pressed for 30 seconds during any of these steps, the controller automatically returns
to temperature display, neither of the SET POINTS being changed.
GB
®
PUBLICACIÓN
Edición 02
1472H100
Digital, 12 V, two-relay, panel mounted thermostat
for Pt 100 probes, up to 600ºC
INSTALLATION AND USER INSTRUCTIONS FOR THE:
GENERAL DESCRIPTION:
Panel-mounted electronic thermostat, suitable for display, control and regulation of heat or cold genera-
tors.
TECHNICAL SPECIFICATIONS:
Temperature range: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -50ºC to 600ºC
Pt 100 probe entry: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ref. AKO-15585, AKO-71726, AKO-71727
Controller accuracy: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
0,5ºC
Ambient working temperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5ºC to 50ºC
Ambient storage temperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -30ºC to 70ºC
INSTALLATION:
Thermostat:
The thermostat must be installed in a place away from vibrations, water and corrosive gas and where the
ambient temperature is within the range in the technical specifications.
For protection level IP65, the joint between the device and the surrounding of the panel space where it is
installed must be properly made.
FRONT PANELS FUNCTIONS:
TEMPERATURE
INDICATION
3
2
1
VERSION:
Fastening:
To fix the unit, place the fasteners 1
over the sliders 2 as shown in the figu-
re. Move the fasteners in the direction
of the arrow. By pressing tab 3, the
fasteners may be moved in the oppo-
site direction to the arrow.
TEMPERATURE SET POINT:
Parameters should only be programmed or chenged by personnel familiar with the operation of the
apparatus and its possibilities where applied.
Programming parameters:
Level 1:
-Hold the + keys down simultaneously for 10 seconds. The PR led will flash and the first parame-
ter, “P00”, will be shown on the display.
-Press the or key to change to the next parameter or previous parameter, respectively.
-When the final parameter EP is on the display, press the + keys simultaneously, the controller will
return to the temperature display and the PR led will stop flashing.
Level 2:
-To see the current value of any parameter, find the one you want and press the + keys simultane-
ously. When it is on display, you can change it with the or keys.
-Press the + keys simultaneously to set the new value. When you do this, the programming will return
to level 1 (parameters).
PROGRAMMING:
PRG
PR
ºC
SET
1
2
LED 2
LED 1
UP key
LED PR
DOWN key
LEVEL 2
VALUES
LEVEL 1
PARAMETERS
DISPLA
Y
V
ALUES
CHANGE
V
ALUES
ENTER
NEW V
ALUES
CURRENT VALUE
NEW VALUE
10 Sec.
PROGRAMMING
EXIT
max.
18 mm
3
2
1
61,5
70,5
28,5
PANEL CUT-OUT
44
AKO-14721
NOTE: If no key is pressed for 30 seconds during any of these steps, the controller automatically returns
to temperature display, none of the parameter values being changed.
MODEL
FUNCTION MOUNTING
RELAYS
POWER
SUPPLY
AKO-14721
Thermostat
Panel-mounted
1: 8A cos
ϕ
=1 (SPDT)
12V
z
,
6
15%, 173 mA
z
2: 8A cos
ϕ
=1 (SPDT)
10 11 12
Pt100
White
Red
Red
Probe:
For correct readings, the probe must be installed in a place free of thermal
effects other than the temperature to be measured or controlled.
This diagram shows how the probe must be connected:
Using this unit without heeding the manufacturer’s instructions may change its safety requirements.
DISPLAY
STATE
DESCRIPTION
OPERATING MESSAGES:
AH
Flashing with
temperature
Temperature above the maximum limit values set in C21 and C22.
AL
Flashing with
temperature
Temperature below the minimum limit values set in C31 and C32.
E1
Steady
Probe short circuited, circuit open >614ºC or <-60.6ºC
EE
Steady
Memory failure
MAINTENANCE:
WARNINGS:
Clean the surface of the controller with a smooth cloth, soap and water. Do not use abrasive detergents,
petrol, alcohol or solvents.
AKO Electromecànica S.A.L. Apartado de Correos, 5. 08800 Vilanova i la Geltrú (Spain)
351472100 Rev. 01 2000 D.L.: B-33.685-00
P00
Operating mode
Selection 0= ON-OFF Switching.
See operating modes.
Set points can be programmed separately for each relay.
Selection 1 = neutral zone.
See operating modes.
PARAMETER DESCRIPTION
RANGE
MIN.
0
MAX.
VALUE
1
0
P01
Operation (cold/heat) of relay 1
Selection 0 = Cold
Selection 1 = Heat
P02
Operation (cold/heat) of relay 2
Selection 0 = Cold
Selection 1 = Heat
0
1
1
P07
Resolution for temperature display.
0=0,1ºC between -50,0 and +99,9ºC rest of the range 1ºC
1= 1ºC for the complete range.
0
1
0
P3
Return to original parameters
1 sets all parameters in the device to the values in the DEF. VALUE column of
this table, then exits programming immediately.
-
C0
Probe calibration (offset)
Increases or decreases the correction to the temperature detected by the ther-
mostat in order to adjust the probe to real temperature.
-20ºC
20ºC
0ºC
-650ºC +650ºC
2ºC
-650ºC +650ºC
2ºC
C11
R1 Differential
Increases or decreases the temperature from that indicated by SET POINT 1 (SP1)
for R1 to be switched on.
See relay 1 operating in ON-OFF switching mode.
C12
R2 Differential
Increase or decreases the temperature from that indicated by SET POINT 2 (SP2)
for R2 to be switched on.
See relay 2 operating in ON-OFF switching mode.
0ºC
325ºC
2ºC
C15
Neutral zone value
Increases/decreases the temperature above or below SET POINT 1 for relays R1
and R2 to act.
See Neutral Zone operating.
xxxºC
600ºC
600ºC
C21
Maximum limit for R1 SET POINT
Relay 1’s SET POINT cannot be established above this figure, the alarm AH being
produced if the temperature is above the value of C21 and C22.
xxxºC
600ºC
600ºC
C22
Maximum limit for R2 SET POINT
Relay 2’s SET POINT cannot be established above this figure, the alarm AH being
produced if the temperature is above the value of C21 and C22.
-50ºC
xxxºC
-50ºC
C31
Minimum limit for R1 SET POINT
Relay 1’s SET POINT cannot be established below this figure, the alarm AL being
produced if the temperature is less than the value of C21 and C22.
-50ºC
xxxºC
-50ºC
C32
Minimum limit for R2 SET POINT
Relay 2’s SET POINT cannot be established below this figure, the alarm AL being
produced if the temperature is less than the value of C21 and C22.
0 min. 99 min.
0 min.
C51
Relay R1 Triggering Delay
Delay for R1 being triggered after the temperature commands its activation.
0 min. 99 min.
0 min.
C52
Relay R2 Triggering Delay
Delay for R2 being triggered after the temperature commands its activation.
0
1
0
C61
R1 status when the probe has failed
0=off
1=on
0
1
0
C62
EP
R2 status when the probe has failed
0=off
1=on
Exit Programming
0
1
1
1
-
DEF.
For Set Point programming, see TEMPERATURE SET POINT.
The figures in the DEF column are the factory settings.
DESCRIPTION OF PARAMETERS:
5 Sec.
PRESENT
SETTING
TEMPERATURE
DISPLAY
NEW
SETTING
PRESENT
SETTING
SP1= Set Point for R1
SP2= Set Point for R2
SELECTION
NEW
SETTING
ENTER
NEW V
ALUE
CHANGE
V
ALUE
DISPLA
Y
SETTINGS
MENU
Holding it down for 5 seconds brings up the temperature adjustment menu.
RELAY CONTROL AND OPERATING MODES
P00=0 ON-OFF Switching
HEAT operation P02=1
ON
OFF
SP2
Temp.
ON
Temp.
OFF
Temp.
ON
Temp.
OFF
SP2 + C12
C12>0
SP2
SP2 - C12
C12<0
ON
OFF
SP2
Temp.
ON
Temp.
OFF
Temp.
ON
Temp.
OFF
SP2 + C12
C12>0
SP2
SP2 - C12
C12<0
ON
COLD operation P01=0
COLD operation P02=0
HEAT operation P01=1
OFF
SP1
Temp.
ON
Temp.
OFF
Temp.
ON
Temp.
OFF
SP1 + C11
C11>0
SP1
SP1 - C11
C11<0
ON
OFF
SP1
Temp.
ON
Temp.
OFF
Temp.
ON
Temp.
OFF
SP1 + C11
C11>0
SP1
SP1 - C11
C11<0
ON
OFF
ON
OFF
SP1 - C15
SP1 + C15
SP1
RELAY 2
RELAY 1
RELAY 2
P00=1 Neutral Zone
RELAY 1
Connections:
Connect plugging terminals according to the rating plate diagram.
The probe and its corresponding cable should NEVER be installed in ducting along with mains, control
or power supply wiring, probe cables
can be extended and no deviation
will appear.
-with independent mounting
-with characteristic of automatic operation action, Type 1.B
-to be used in clean situation
Control device classification: