Functions:

UP key
During programming, increases
the figure being displayed.

DOWN key
During programming, lowers 
the figure being displayed.

+        Held down simultaneously for 10 seconds brings up the programming menu.

+        Held down simultaneously enters the new value.

Indicator LEDs:

LED 1 

constant: Shows relay 1 is on.

flashing: Means relay 1 should be on according to the temperature detected by the probe, 

but is not, owing to a programming condition.

LED 2 

constant: Shows relay 2 is on.

flashing: Means relay 2 should be on according to the temperature detected by the probe, 

but is not, owing to a programming condition.

LED PR 

flashing: Programming set point or parameters.

The default (factory) setting for
SET POINTS 1 and  2 are 0ºC

-  Hold the      key down for 5 seconds. This opens the SP1 or SP2 setting menu (the PR led will flash).
- Press the 

or 

key to select SET POINT 1 or SET POINT 2.

- Press the 

keys simultaneously to show the setting you want to change.

- Press the 

or 

keys to change the SET POINT to the figure you want.

- Press the 

keys simultaneously to enter the new figure. When you do this, the display shows

the temperature again and the PR led stops flashing.

NOTE: If no key is pressed for 30 seconds during any of these steps, the controller automatically returns
to temperature display, neither of the SET POINTS being changed.

GB

®

PUBLICACIÓN

Edición  02

1472H100

Digital, 12 V, two-relay, panel mounted thermostat
for Pt 100 probes, up to 600ºC

INSTALLATION AND USER INSTRUCTIONS FOR THE:

GENERAL DESCRIPTION:

Panel-mounted electronic thermostat, suitable for display, control and regulation of heat or cold genera-
tors.

TECHNICAL SPECIFICATIONS:

Temperature range: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -50ºC to 600ºC
Pt 100 probe entry: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ref. AKO-15585, AKO-71726, AKO-71727
Controller accuracy: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

6

0,5ºC

Ambient working temperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5ºC to 50ºC
Ambient storage temperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -30ºC to 70ºC

INSTALLATION:

Thermostat:
The thermostat must be installed in a place away from vibrations, water and corrosive gas and where the
ambient temperature is within the range in the technical specifications.

For protection level IP65, the joint between the device and the surrounding of the panel space where it is
installed must be properly made.

FRONT PANELS FUNCTIONS:

TEMPERATURE 

INDICATION

3

2

1

VERSION:

Fastening:
To fix the unit, place the fasteners 1
over the sliders as shown in the figu-
re. Move the fasteners in the direction
of the arrow. By pressing tab 3, the
fasteners may be moved in the oppo-
site direction to the arrow.

TEMPERATURE SET POINT:

Parameters should only be programmed or chenged by personnel familiar with the operation of the
apparatus and its possibilities where applied.

Programming parameters:

Level 1:

-Hold the     +      keys down simultaneously for 10 seconds. The PR led will flash and the first parame-

ter, “P00”, will be shown on the display.

-Press the      or      key to change to the next parameter or previous parameter, respectively.

-When the final parameter EP is on the display, press the      +      keys simultaneously, the controller will

return to the temperature display and the PR led will stop flashing.

Level 2:

-To see the current value of any parameter, find the one you want and press the     +     keys simultane-

ously. When it is on display, you can change it with the     or     keys.

-Press the     +     keys simultaneously to set the new value. When you do this, the programming will return

to level 1 (parameters).

PROGRAMMING:

PRG

PR

ºC

SET

1

2

LED 2

LED 1

UP key

LED PR

DOWN key

LEVEL 2
VALUES

LEVEL 1 

PARAMETERS

DISPLA

V

ALUES

CHANGE 

V

ALUES

ENTER 

NEW V

ALUES

CURRENT VALUE

NEW VALUE

10 Sec.

PROGRAMMING

EXIT

max. 

18 mm

3

2

1

61,5

70,5

28,5

PANEL CUT-OUT

44

AKO-14721

NOTE: If no key is pressed for 30 seconds during any of these steps, the controller automatically returns
to temperature display, none of the parameter values being changed.

MODEL

FUNCTION MOUNTING

RELAYS 

POWER 

SUPPLY

AKO-14721

Thermostat

Panel-mounted

1: 8A cos 

ϕ 

=1 (SPDT)

12V 

z

6

15%, 173 mA

z

2: 8A cos 

ϕ 

=1 (SPDT)

10 11 12

Pt100

White

Red

Red

Probe:
For correct readings, the probe must be installed in a place free of thermal
effects other than the temperature to be measured or controlled.

This diagram shows how the probe must be connected:

Using this unit without heeding the manufacturer’s instructions may change its safety requirements.

DISPLAY

STATE

DESCRIPTION

OPERATING MESSAGES:

AH

Flashing with 
temperature

Temperature above the maximum limit values set in C21 and C22.

AL

Flashing with 
temperature

Temperature below the minimum limit values set in C31 and C32.

E1

Steady

Probe short circuited, circuit open >614ºC or <-60.6ºC

EE

Steady

Memory failure

MAINTENANCE:

WARNINGS:

Clean the surface of the controller with a smooth cloth, soap and water. Do not use abrasive detergents,
petrol, alcohol or solvents.

AKO Electromecànica S.A.L. Apartado de Correos, 5.  08800 Vilanova i la Geltrú (Spain)

351472100 Rev. 01 2000    D.L.: B-33.685-00

P00

Operating mode
Selection 0= ON-OFF Switching.
See operating modes.
Set points can be programmed separately for each relay.

Selection 1 = neutral zone.
See operating modes.

PARAMETER    DESCRIPTION

RANGE

MIN.

0

MAX.

VALUE

1

0

P01

Operation (cold/heat) of relay 1
Selection 0 = Cold
Selection 1 = Heat 

P02

Operation (cold/heat) of relay 2
Selection 0 = Cold
Selection 1 = Heat

0

1

1

P07 

Resolution for temperature display.
0=0,1ºC between -50,0 and +99,9ºC rest of the range 1ºC
1=  1ºC for the complete range.

0

1

0

P3

Return to original parameters
1 sets all parameters in the device to the values in the DEF.  VALUE column of
this table, then exits programming immediately.

-

C0

Probe calibration (offset)
Increases or decreases the correction to the temperature detected by the ther-
mostat in order to adjust the probe to real temperature.

-20ºC

20ºC

0ºC

-650ºC +650ºC

2ºC

-650ºC +650ºC

2ºC

C11

R1 Differential
Increases or decreases the temperature from that indicated by SET POINT 1 (SP1)
for R1 to be switched on.
See relay 1 operating in ON-OFF switching mode.

C12

R2 Differential
Increase or decreases the temperature from that indicated by SET POINT 2 (SP2)
for R2 to be switched on.
See relay 2 operating in ON-OFF switching mode.

0ºC

325ºC

2ºC

C15

Neutral zone value
Increases/decreases the temperature above or below SET POINT 1 for relays R1
and R2 to act.
See Neutral Zone operating.

xxxºC

600ºC

600ºC

C21

Maximum limit for R1 SET POINT
Relay 1’s SET POINT cannot be established above this figure, the alarm AH being
produced if the temperature is above the value of C21 and C22.

xxxºC

600ºC

600ºC

C22

Maximum limit for R2 SET POINT
Relay 2’s SET POINT cannot be established above this figure, the alarm AH being
produced if the temperature is above the value of C21 and C22.

-50ºC

xxxºC

-50ºC

C31

Minimum limit for R1 SET POINT
Relay 1’s SET POINT cannot be established below this figure, the alarm AL being
produced if the temperature is less than the value of C21 and C22.

-50ºC

xxxºC

-50ºC

C32

Minimum limit for R2 SET POINT
Relay 2’s SET POINT cannot be established below this figure, the alarm AL being
produced if the temperature is less than the value of C21 and C22.

0 min. 99 min.

0 min.

C51

Relay R1 Triggering Delay
Delay for R1 being triggered after the temperature commands its activation.

0 min. 99 min.

0 min.

C52

Relay R2 Triggering Delay
Delay for R2 being triggered after the temperature commands its activation.

0

1

0

C61

R1 status when the probe has failed
0=off
1=on

0

1

0

C62

EP

R2 status when the probe has failed
0=off
1=on

Exit Programming

0

1

1

1

-

DEF.

For Set Point programming, see TEMPERATURE SET POINT.
The figures in the DEF column are the factory settings. 

DESCRIPTION OF PARAMETERS:

5 Sec.

PRESENT

SETTING

TEMPERATURE

DISPLAY

NEW 

SETTING

PRESENT

SETTING

SP1= Set Point for R1

SP2= Set Point for R2

SELECTION

NEW 

SETTING

ENTER 

NEW V

ALUE

CHANGE

V

ALUE

DISPLA

Y

SETTINGS

MENU

Holding it down for 5 seconds brings up the temperature adjustment menu.

RELAY CONTROL AND OPERATING MODES

P00=0 ON-OFF Switching 

HEAT operation  P02=1

ON

OFF

SP2

Temp. 

ON

Temp.

OFF

Temp. 

ON

Temp.

OFF

SP2 + C12

C12>0

SP2

SP2 - C12

C12<0

ON

OFF

SP2

Temp. 

ON

Temp.

OFF

Temp. 

ON

Temp. 

OFF

SP2 + C12

C12>0

SP2

SP2 - C12

C12<0

ON

COLD operation  P01=0

COLD operation  P02=0

HEAT operation  P01=1

OFF

SP1

Temp. 

ON

Temp.

OFF

Temp. 

ON

Temp.

OFF

SP1 + C11

C11>0

SP1

SP1 - C11

C11<0

ON

OFF

SP1

Temp. 

ON

Temp.

OFF

Temp. 

ON

Temp.

OFF

SP1 + C11

C11>0

SP1

SP1 - C11

C11<0

ON

OFF

ON

OFF

SP1 - C15

SP1 + C15

SP1

RELAY 2

RELAY 1

RELAY 2

P00=1 Neutral Zone

RELAY 1

Connections:
Connect plugging terminals according to the rating plate diagram.

The probe and its corresponding cable should NEVER be installed in ducting along with mains, control
or power supply wiring, probe cables 
can be extended and no deviation 
will appear.

-with independent mounting
-with characteristic of automatic operation action, Type 1.B
-to be used in clean situation

Control device classification: