DECK OVEN CONTROLLER USER MANUAL
7
8. DEVICE MALFUNCTION SITUATION
A-1:
Upper thermocuple is not installed or the temperature of area that is read by Upper
Thermocupe is more than 500
o
C.
Solution: Oven must be completely de-energised. Thermocuple connectio, resistance relay and
resistance contactor should be controlled.
A-2:
Sub thermocuple is not installed or the temperature of area that is read by Sub Thermocupe is
more than 500
o
C.
Solution: Oven must be completely de-energised. Thermocuple connectio, resistance relay and
resistance contactor should be controlled.
A-3:
Internal upper temperature is more than 350
o
C.
Solution: Oven must be completely de-energised. Thermocuple connection, resistance relay and
resistance contactor should be controlled.
A-4:
Internal upper temperature is more than 350
o
C.
Solution: Oven must be completely de-energised. Thermocuple connection, resistance relay and
resistance contactor should be controlled.
A-5:
Internal temperature of oven panel is more than 70
o
C.
Solution : Oven panel ventilation should be checked.
9.DEVICE MALFUNCTION OPTION
E-1:
The raising steam button was touched while steam blow is cold.
E-2:
While the temperature below raising steam temperature (100
o
C), raising steam button was
touched.
E-3:
, Raising steam button was touched before raising steam period completed.(15sn)