Subject to change without notice | 83019600bUK – Translation of the original operating manual | ait-deutschland GmbH
11.3
Technical specifications
L…Split
Outdoor module
L6 Split
L8 Split
L12 Split
Output data according to EN 14511 ΔT5K
Outdoor
temp./ Supply
temp.
Heating
Capacity / power input / COP (kW/kW/-)
at nominal flow
7/35 °C
(floor)
2,67/0,5/4,85
3,86/0,83/4,65
5,21/1,09/4,78
2/35 °C
(floor)
2,32/0,55/4,2
5,11/1,36/3,76
6,91/1,79/3,86
-7/35 °C
(floor)
4,60/1,79/2,57
6,60/2,46/2,68
9,00/3,27/2,75
7/45 °C
2,28/0,63/3,62
3,70/1,00/3,70
5,00/1,31/3,82
2/45 °C
1,93/0,67/2,88
5,03/1,70/2,96
6,80/2,24/3,04
Cooling
Capacity / Power input / EER (kW/kW/-)
at maximum flow
27/7 °C
5,87/1,65/3,56
7,52/2,37/3,17
9,87/3,16/3,13
27/18 °C
7,98/1,77/4,52
11,20/3,20/3,50
11,70/3,32/3,52
35/7 °C
4,86/1,86/2,61
7,10/2,65/2,68
9,45/3,41/2,77
35/18 °C
7,03/2,03/3,45
9,19/2,98/3,08
11,20/3,58/3,12
Electrical data
Rated voltage
230V 50 Hz, 230V 2WS 50 Hz
Max. current
A
rms
15
16
23
Recommended fuse rating
A
rms
16
16
25
Starting current
A
rms
5
Max fan flow (heating, nominal)
m³/h
2 530
3 000
4 380
Fan rating
W
50
86
Drain pan heater (integrated)
W
110
100
120
Defrosting
Reverse cycle
Enclosure class
IP24
Refrigerant circuit
Type of refrigerant
R410A
GWP refrigerant
2 088
Compressor
Twin Rotary
Refrigerant quantity
kg
1,5
2,55
2,90
CO
2
-equivalent
t
3,13
5,32
6,06
Cut-out value, pressure switch, high pressure
MPa (Bar)
-
4,15 (41,5)
Breaking value high pressure
MPa (Bar)
4,15 (41,5)
Cut-out value, pressure switch, lowpressure
(15 s)
MPa (Bar)
-
0,079 MPa (0,79)
Max. length, refrigerant pipe, one way
m
30*
Max height difference, refrigerant pipe
m
7
Dimensions, refrigerant pipe
Gas pipe: OD12,7 (1/2")
Fluid pipe: OD6,35 (1/4")
Gas pipe: OD15,88 (5/8")
Fluid pipe: OD9,52 (3/8")
Pipe connections
Pipe connection option
Right-hand side Right-hand side
Right /bottom /reverse
Pipe connections
Flare
* L6 Split: If the length of the refrigerant pipes exceeds 15 m, extra refrigerant must be added at a rate of 0.02 kg/m.
L8 Split, L12 Split: If the length of the refrigerant pipes exceeds 15 metres, extra refrigerant must be added at a rate of 0.06 kg/m.