background image

 

 

 

 

   

ES 

EN 

FR 

IT 

PT 

DE 

LUTRON CONFIGURATION 

To perform the integration with the Airzone system in the HomeWorks QS software, please follow the steps below: 

1.

 

Define the HVAC zones in the software in the menu 

design – loads

 and select HVAC zones.  

Important

: On zoned ducted units the Fan Speed option enabled must be Auto. The “Auto” Operating Mode is only available 

for Airzone systems in North America.

 

 

2.

 

For Palladiom thermostats, add them to the rooms in the 

design – controls

 screen. After adding a thermostat, you 

must assign the HVAC zone it will control in the 

Remote Zone

 setting. 

 

3.

 

Define  the Airzone-Lutron interface in the 

design – equipment

  screen. Add a “3

rd

  Party HVAC” device and name it 

“Airzone System”. In the 

Manufacturer

 drop down, select “Generic (via integration)”. For 

Setpoint type

, select “Dual”. In 

the output table, click on Assign and add all the HVAC zones you created previously.  

Note

: The UID must be unique for each zone. Set the minimum and maximum Setpoint at 19ºC and 30ºC respectively. Set 

the same differential value of Minimum Heat/Cool as Lutron System in case of Setpoint Dual. 

 

4.

 

 On the navbar, click 

Tools

 and select 

Configure Integration

 

 

Содержание Lutron

Страница 1: ...Installation Manual...

Страница 2: ...ration with Lutron Palladiom thermostat to control the HVAC zone 6 Configuration with Airzone thermostat 6 Lutron Configuration 7 Airzone system Configuration 8 System configuration for ACUAZONE IBPRO...

Страница 3: ...e control of the conditioning of each zone associated from Lutron Keypads devices and the control of time schedules both from the HomeWorks QS Processor and from the Lutron Connect App The Airzone Lut...

Страница 4: ...temperatures Storage 20 to 70 C Operation 0 to 50 C Operating humidity range 5 to 90 non condesing W H D Meaning D5 Ethernet connected Blinking Green D4 Ethernet activity Blinking Yellow D7 Data tran...

Страница 5: ...hernet cable should be connected to the Airzone Lutron interface Once the control board has the interface connected it will auto detect the presence of the interface and will automatically set the par...

Страница 6: ...zone 1 02 for Airzone zone 2 Up to 32 Airzone zones per system based on the type of the system Example A Palladiom thermostat DEVICE Integration ID for the Airzone system 1 and for zone 1 will be 2010...

Страница 7: ...r adding a thermostat you must assign the HVAC zone it will control in the Remote Zone setting 3 Define the Airzone Lutron interface in the design equipment screen Add a 3rd Party HVAC device and name...

Страница 8: ...rmat 1XXYY as described on page 6 6 While still in the Configure Integration screen select the tab Telnet Logins Add the Username and Passphrase the Airzone Lutron interface will use to make a Telnet...

Страница 9: ...and select system settings once in find and press BACnet to access Inside the menu press the settings icon and set the static IP address for example 192 168 100 207 LOAD THE CONFIGURATION INTO THE HOM...

Страница 10: ...ce is blinking 2 The D7 and D8 LEDs are alternately blinking 3 The correct connection between the Airzone Lutron Interface in the Airzone Main Control Board THE AIRZONE LUTRON INTERFACE CANNOT BE CONN...

Страница 11: ...ax 34 902 400 446 http www myzone airzone es Parc Tertiaire Silic Inmeuble Panama 45 Rue Villeneuve 94573 Rungis France T l phone 33 184 884 695 Fax 33 144 042 114 http www myzone airzonefrance fr Via...

Отзывы: