3.2.2. Connection
SuperMaster controller
is an element that is connected to the domotic bus of every system
controller
(Fig. 3).
Fig. 3
In case of having a Production unit controller AZXCCPC in the installation,
connect every
system to the input domotic bus on the AZXCCPC and the SuperMaster controller to the
output bus on the AZXCCPC
(Fig. 3).
Use 0,22mm
2
wires for communication pins and 0,50mm
2
wires for power supply.
Wall-mounted controller is connected by means of metallic flanges placed on the back
protection case. To fit wires, unscrew the screws; insert wire under flange paying attention for
false contacts and to the
color code and the associated letter code printed
(Fig. 4).
Fig. 4
Wall-embedded controller is connected by means of a four pin aerial connector. Find it at the
back of the controller. Fit wires with the screws on the connector,
paying attention to the
associated color and letter code
(Fig. 4).