31
Control relays
This device has 6 relays for controlling the installation. The characteristics of the control relays are I
max
of 10 A at 110/230 Vac
(voltage-free. Note that to control elements with a greater power, it is recommended to use contactors in accordance with the
power required.
Important:
Remember to connect the neutral connector directly from the circuit to the element to be controlled.
Depending on the type of installation, the control relays will follow a different logic:
Aerothermal
Mode
Demand
Control Relays
FRIO_Y
CALORB_W
AIRE_Y
RADIANTE_Y
AIRE_W
RADIANTE_W
Stop
Off
--
--
--
--
--
--
Cooling
mode
Air
ON
--
ON
--
--
--
Radiant
ON
--
--
ON
--
--
Off
--
--
--
--
--
--
Heating
mode
Air
--
ON
--
--
ON
--
Radiant
--
ON
--
--
--
ON
Off
--
--
--
--
--
--
2 pipes / 3/4 pipes
Mode
Demand
Control Relays
FRIO_Y
CALORB_W
AIRE_Y
RADIANTE_Y
AIRE_W
RADIANTE_W
Stop
Off
--
--
--
--
--
--
Cooling
mode
Air
ON
--
ON
--
--
--
Radiant
ON
--
--
ON
--
--
Off
ON
--
--
--
--
--
Heating
mode
Air
--
ON
--
--
ON
--
Radiant
--
ON
--
--
--
ON
Off
--
ON
--
--
--
--
RadianT
Mode
Demand
Control Relays
FRIO_Y
CALORB_W
AIRE_Y
RADIANTE_Y
AIRE_W
RADIANTE_W
Stop
Off
--
--
--
--
--
--
Cooling
mode
Radiant
ON
--
--
ON
--
--
Off
--
--
--
--
--
--
Heating
mode
Radiant
--
ON
--
--
--
ON
Off
--
--
--
--
--
--
Dehumidifier
activation
Radiant
ON
--
ON
--
--
--
Off
Important:
To guarantee the optimization of the production temperature of the aerothermal units, these device combinations
do not generate demand to the production control board:
-
Communication gateway (AZX6QADAPTxxx) in Flexa 3.0, Innobus Pro6, Acuazone and Innobus Pro32 main control
boards.
-
Communication gateway for electromechanical units (AZDI6MCIFR [C/R]) in Acuazone and Innobus Pro32 systems
configured as zoning or combined systems.
-
Airzone infrared individual unit zone module (AZDI6MCIFRC) in Acuazone and Innobus Pro32 systems configured as
zoning or combined systems.
-
Airzone individual unit modules (AZDI6MCxxxC) in Acuazone and Innobus Pro32 systems configured as zoning or
combined systems.
Содержание 8435418928905
Страница 1: ...r e b m u N e g a P d r a o b p il C Installation Manual RADIANT365 AZRA6RADIANT AZRA6CM1VALC...
Страница 2: ...1 8 ZONES AZRA6RADIANT AZRA6CM1VALC...
Страница 35: ...36 Blueface Think Important Use to confirm and to return...
Страница 49: ...50 NAVIGATION TREES NAVIGATION TREE BLUEFACE THERMOSTAT...
Страница 50: ...51 NAVIGATION TREE THINK THERMOSTAT...