Marvair MAA/MGA Wall Mount AC Installation & Operation Manual
09/2021 Rev.15
7
1.3
Serial Number Date Code
20 = 2020
01 = January
05 = May
09 = September
21 = 2021
02 = February
06 = June
10= October
22 = 2022
03= March
07 = July
11 = November
23 = 2023
04 = April
08 = August
12 = December
1.4
Air Flow, Weights and Filter Sizes
Complete electrical and performance specifications and dimensional drawings are in the Marvair Wall
Mount Air Conditioner Product Data Sheets.
Note:
Follow local codes and standards when designing duct runs to deliver the required airflow.
Minimize noise and excessive pressure drops caused by duct aspect ratio changes, bends, dampers and
outlet grilles in duct runs.
Model
0.10
0.15
0.20
0.25
0.30
0.40
0.50
MAA1018
685
670
670
642
640
600
MAA1020
800
785
770
725
680
600
MAA1024
800
785
770
725
680
600
500
MAA1030
1200
1150
1100
1050
1000
900
800
MAA1036
1290
1230
1170
1115
1060
1000
920
MAA1042
1500
1430
1360
1295
1230
1160
1070
MAA1048
1950
1900
1850
1815
1760
1680
1590
MAA1060/MAA2072 & MGA1072
1900
1850
1800
1700
1600
1500
1350
Values in bold are the minimum air flow.
Air flow ratings of 208-230 volt units are at 230v. Air flow ratings of 460 volt units are at 460 volts. Operation of units at a voltage different from the
rating point will affect air flow
.
Table 1. CFM @ External Static Pressure (Wet Coil) (IWG)
Model
INCHES
MILLIMETERS PART NUMBER FILTERS PER UNIT MERV RATING
MAA1018
14 x 12 1
356 x 305 x 25
P/80122
1
N/A
MAA1020/1024
16 x 25 x 2
406 x 635 x 51
80137
1
8
MAA1024/1030/1036 "B2" INTERNAL
16 x 30 x 1
406 x 762 x 25
80136
1
N/A
MAA1024 "B2" RETURN GRILLE
11½ x 19½ x 1
292 x 495 x 25
91983
1
N/A
MAA1030/1036 & MAA2072
18 x 30 x 2
457 x 762 x 51
93184
1
8
MAA1030/1036 "B2" RETURN GRILLE
27½ x 13½ x 1 699 x 343 x 25
80769
1
N/A
MAA1042/1048
36½ x 22 x 2
927 x 559 x 51
80162
1
8
MAA1060
18 x 24 x 2
457 x 610 x 51
81257
2
8
MGA1072
18 x 24 x 2
457 x 610 x 51
81257
2
8
Table 2. Return Air Filter Sizes
Model
Weight
Base
w/Economizer w/3 Phase w/Economizer & 3 Phase
MAA1018
Pounds (Kilograms)
265 (120)
N/A
N/A
N/A
MAA1020/MAA1024
Pounds (Kilograms)
337 (153)
357 (162)
356 (161)
376 (171)
MAA1024/1030 "B2"
Pounds (Kilograms)
378 (171)
400 (181)
397 (180)
419 (190)
MAA1030/MAA1036
Pounds (Kilograms)
397 (180)
419 (190)
416 (189)
438 (199)
MAA1036 "B2"
Pounds (Kilograms)
380 (172)
403 (183)
418 (190)
441 (200)
MAA1042/MAA1048
Pounds (Kilograms)
453 (205)
476 (216)
491 (223)
514 (233)
MAA1060
Pounds (Kilograms)
469 (213)
492 (223)
522 (237)
545 (247)
MAA2072
Pounds (Kilograms)
717 (325)
740 (336)
770 (349)
793 (360)
MGA1072
Pounds (Kilograms)
571 (259)
594 (269)
624 (283)
647 (293)
Table 3. Installed Weights for Marvair Wall Mount AC Units
1.5 General Operation
Model
Ventilation Configuration
Temperature Range
Non-Economizer
Standard ("N")
20ºF – 131ºF (-7ºC – 55ºC)
Desert Duty ("ND")
20ºF – 131ºF (-0ºC – 55ºC)
Extreme Duty ("NE"), 60 Hz Only
0ºF – 131ºF (-18ºC – 55ºC)
With Economizer
Standard ("CE")
-40ºF – 131ºF (-40ºC – 55ºC)
Desert Duty ("CD")
-40ºF – 131ºF (-40ºC – 55ºC)
Extreme Duty ("CE"), 60 Hz Only
-40ºF – 131ºF (-40ºC – 55ºC)
Table 4. Ambient Temperature Operating Range