Parameter
Default Value Setting Range Unit Alarm Conditions
No Alarm
- -
- -
- -
There is no alarm
HTemp.Alarm
40
[25 ~ 80]
ºC
The internal cycle temperature
exceeds the high temperature
alarm point
LTemp.Alarm
0
[-20 ~ 15]
ºC
The internal cycle temperature
exceeds the low temperature alarm
point
In.Ts.Fault
- -
- -
- -
Internal cycle temperature sensor
failure
Out.Ts.Fault
- -
- -
- -
Exterior cycle temperature sensor
failure
Pi.Ts.Fault
- -
- -
- -
Evaporator sensor failure
Con.Ts.Fault
- -
- -
- -
Condenser sensor failure
HP.Alarm
- -
- -
- -
The condenser pressure is too high
HP.Alm.Lock
- -
- -
- -
The system cooling pressure is
frequently too high
Door.Open
- -
- -
- -
Cabinet door is opened (optional)
Evap Frost
0
- -
ºC
The evaporator temperature is too
low
VAC.Over
253
- -
V
AC voltage is too high
VAC.Under
187
- -
V
AC voltage is too low
Note:
The actual parameters have been set upon delivery according to the customer’s
requirement.
Table 8. Alarm Parameters and Settings
3.7 Monitoring
The air conditioner communicates with the upper monitor through the RS485
communication interface. Or users can check the air conditioner’s running state by
viewing the display screen directly and change its running parameters.