32
ICE CEA/CGA1012–1060 Wall Mount AC I&O Manual
03/2021 Rev.1
Additional Items Needed:
Additional hardware and miscellaneous supplies (not furnished by ICE) are needed for installation.
For example, the list below contains approximate quantities of items typically needed for mounting
a unit on a wood frame wall structure. Concrete or fiberglass structures have different requirements.
(10)
3/8" carriage head mounting bolts
for unit mounting flanges. The length needed is typically
the wall thickness plus one inch.
(20)
3/8" washers
(10)
3/8" hex nuts
(6)
3/8" x 2-1/2" lag screws
for bottom bracket
•
Silicone Sealer
to seal around cracks and openings
•
Minimum 5 conductor low voltage multicolored wire cable
(i.e. thermostat wire)
•
Appropriate electrical supplies
such as
conduit, electrical boxes, fittings,
wire connectors,
etc.
•
High voltage wire
, sized to handle the MCA (minimum circuit ampacity) listed on the data
plate.
•
Over-Current Protection Device
sized in accordance with the MFS (maximum fuse size) listed
on the unit data plate.
WARNING - FIRE HAZARD
Improper adjustment, alteration, service, maintenance or installation could cause serious
injury, death and/or property damage.
Installation or repairs made by unqualified persons could result in hazards to you and
others. Installation MUST conform with local codes or, in the absence of local codes, with
codes of all governmental authorities have jurisdiction.
The information contained in this manual is intended for use by a qualified service agency
that is experienced in such work, is familiar with all precautions and safety procedures
required in such work, and is equipped with the proper tools and test instruments.
3.4 Porting and Duct Work
General Information
Note: The following instructions are for general guidance only. Due to the wide variety of installation
possibilities, specific instructions will not be given. When in doubt, follow standard and accepted
installation practices, or contact Technical Support for additional assistance.
Wall Openings (CEA1012 air conditioner, all CEA1024-1060, and all CEA1030-1060)
Measure the dimensions of the supply and return ports on the unit.
Cut the openings in the exterior wall for the supply and return.
IMPORTANT:
All units with electric
heat must have 1" (25.4mm) clearance on all four sides of the supply outlet duct flange on the
unit. The 1" (25.4mm) clearance must extend on all sides of the supply duct for the first 3 feet (1
meter) from the unit.
IMPORTANT: ICE requires a minimum of 1" (25.4mm)
from the surface of any supply ducts to
combustible material for the first 3 feet (1 meter) of the duct.
Wall Openings (CEA1012 air conditoners with the factory installed economizer)
The back panel of the one ton air conditioner with the factory installed economizer is designed to have
a single opening for the supply and return air. From the factory, the back panel is configured for a 19”W
x 21”H (483 mm x 533 mm) opening, but can be easily changed in the field for a 28”W x 19”H (711
mm x 483 mm) opening. Note: the opening is larger than the wall sleeve to allow a one inch clearance
on all four sides of the wall sleeve to any combustible material. This clearance is
required
per National
Fire Protection Association (NFPA) standards 90A & 90B for any unit with electric heat.