![Airwell YUDE024 Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/airwell/yude024/yude024_service-manual_2879962014.webp)
PRODUCT DATA SHEET
SM YUDE 2-A.1 GB
2-7
2.7
AWSI-DBDE036-N11 // AWAU-YUDE036-H11
Model Indoor Unit
AWAU-DBDE036-N11
Model Outdoor Unit
AWAU-YUDE036-H11
Installation Method of Pipe
Flared
Characteristics
Units
Cooling
Heating
Average
Capacity
(1)
kW
10,0(3,2-11,5)
12,0(2,9-14,5)
Pdesign
kW
10,0
10,4
SEER / SCOP
(2)
W/W
5.1
3.8
Energy efficiency class
A
A
Annual energy consumption
kWh
687
3832
Tbiv
o
C
N/A
-7
Tol
o
C
N/A
-15
Power supply
V/Ph/Hz
220-240V/Single/50Hz
Circuit breaker rating(Indoor-Outdoor)
A
10-32
Rated power input (Maximum power input)
kW
4,65
4,75
Rated current (Maximum current)
A
21,5
22,0
INDOOR
Fan type & quantity
Centrifugal fan-2
Fan speeds
H/M/L
RPM
1380/1350/1200/1050
1380/1350/1200/1050
Air flow
(3)
H/M/L
m3/hr
2100/1950/1800/1700
2100/1950/1800/1700
External static
pressure
Min-Max
Pa
37(0-150)
Sound power level
(4)
H/M/L
dB(A)
64
Sound pressure level
(5)
H/M/L
dB(A)
53/52/48/44
Moisture removal
l/hr
2,3
Condensate drain tube I.D
mm
20mm
Dimensions
WxHxD
mm
1226x290x775
Weight
kg
46
Package dimensions
WxHxD
mm
1338x877x305
Packaged weight
kg
63
Units per pallet
units
6
Stacking height
units
6
OUTDOO
R
Refrigerant control
EEV
Compressor type, model
Rotary DC Inverter
Fan type & quantity
Axial x 1
Fan speeds
H/L
RPM
900
Air flow
H/L
m3/hr
5300
Sound power level
(4)
H/L
dB(A)
70
Sound pressure level
(5)
H/L
dB(A)
63
Dimensions
WxHxD
mm
1107x1100x440
Weight
kg
92
Package dimensions
WxHxD
mm
1158x1235 x493
Packaged weight
kg
100
Units per pallet
Units
6
Stacking height
Units
2
Refrigerant type
R410A
Refrigerant charge (standard connecting
tubing length)
kg(5m)
3,5
Additional charge per 1 meter
gr / 1m
5m<L<30m 60g/m
Connections
between units
Liquid line
In.(mm)
3/8"(9.53)
Suction line
In.(mm)
5/8"(15.88)
Max.tubing length
m.
Max.30
Max.height difference
m.
Max.15
Operation control type
Remote control/Wired Remote control
Heating elements
kW
-
Others
-
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
(2) SEER / SCOP calculation accordance with EN14825.
(3) Airflow in ducted units; at nominal external static pressure.
(4) Sound power in ducted units is measured at air discharge.
(5) Sound pressure level measured at 1.4 meter distance from unit.
Содержание YUDE024
Страница 21: ...PERFORMANCE DATA SM YUDE 2 A 1 GB 5 1 5 PERFORMANCE DATA...
Страница 25: ...WIRING DIAGRAMS SM YUDE 2 A 1 GB 8 1 8 WIRING DIAGRAMS 8 1 AWAU YUDE024 H11 AWAU YUDE030 H11 M P P...
Страница 26: ...WIRING DIAGRAMS 8 2 SM YUDE 2 A 1 GB 8 2 AWAU YUDE036 H11...
Страница 27: ...WIRING DIAGRAMS SM YUDE 2 A 1 GB 8 3 8 3 AWAU YUDE036 H13 TBD...
Страница 28: ...WIRING DIAGRAMS 8 4 SM YUDE 2 A 1 GB 8 4 AWSI CADE024 030 036 N11 For model 30 42...
Страница 30: ...WIRING DIAGRAMS 8 6 SM YUDE 2 A 1 GB 8 6 AWSI DBD024 030 036 N11...
Страница 54: ...EXPLODED VIEWS AND PARE PARTS LISTS 13 4 SM YUDE 2 A 1 GB 13 4 Exploded view of Indoor unit AWSI DBDE036 N11...
Страница 62: ...EXPLODED VIEWS AND PARE PARTS LISTS 13 12 SM YUDE 2 A 1 GB 13 12 Exploded view of Indoor unit AWSI FADE024 N11...
Страница 70: ...EXPLODED VIEWS AND PARE PARTS LISTS 13 20 SM YUDE 2 A 1 GB 13 20 Exploded view of Outdoor unit AWAU YUDE036 H11...
Страница 72: ...APPENDIX SM YUDE 2 A 1 GB 14 1 14 APPENDIX APPENDIX...