TROUBLESHOOTING
SM FSF048 1-A.0 GB
12.
TROUBLESHOOTING
12.1
ELECTRICAL & CONTROL TROUBLESHOOTING
12.1.1
Precautions before Performing Inspection or Repair
Be cautious during installation and maintenance. Do operation following the regulations to avoid
electric shock and casualty or even death due to drop from high attitude.
*
Static maintenance
is the maintenance during de-energization of the air conditioner.
For static maintenance, make sure that the unit is de-energized and the plug is disconnected.
*
Dynamic maintenance
is the maintenance during energization of the unit. Before dynamic
maintenance, check the electricity and ensure that there is ground wire on the site. Check if
there is electricity on the housing and connection copper pipe of the air conditioner with voltage
tester. After ensure insulation place and the safety, the maintenance can be performed.
Take sufficient care to avoid directly touching any of the circuit parts without first turning off the
power. At time such as when the circuit board is to be replaced, place the circuit board assembly
in a vertical position. Normally,diagnose troubles according to the trouble diagnosis procedure as
described below.(Refer to the check points in servicing written on the wiring diagrams attached
to the indoor/outdoor units.)
Precautions when inspecting the control section of the outdoor unit
:
A large-capacity electrolytic capacitor is used in the outdoor unit controller (inverter).Therefore,if
the power supply is turned off, charge(charging voltage DC280V to 380V)remains and discharging
takes a lot of time. After turning off the power source,if touching the charging section before
discharging, an electrical shock may be caused.
The outdoor unit can not be started up until the unit is de-energized for 20min
12.1.2
Confirmation
12.1.2.1 Confirmation of Power Supply Confirm that the power breaker
operates(ON) normally;
12.1.2.2 Confirmation of Power Voltage Confirm that power voltage is AC380-
415V+/-10% for threee phase. If power voltage is not in this range, the unit
may not operate normally.