Installation
Page 138
8. Additional Refrigerant Charge
•
After the vacuum drying process is carried out, the
additional refrigerant charge process need to be
performed.
•
The outdoor unit is factory charged with refrigerant.
The additional refrigerant charge volume is decided
by the diameter and length of the liquid pipe be-
tween indoor and outdoor unit. Refer the following
formula to calculate the charge volume.
Diameter of liquid pipe (mm)
Formula
6.35
V=12g/m×(L-5)
9.52
V=24g/m×(L-5)
V:
Additional refrigerant charge volume (g).
L :
The length of the liquid pipe (m).
Note:
•
Refrigerant may only be charged after performed
the vacuum drying process.
•
Always use gloves and glasses to protect your hands
and eyes during the charge work.
•
Use electronic scale or fluid infusion apparatus to
weight refrigerant to be recharged. Be sure to avoid
extra refrigerant charged, it may cause liquid ham-
mer of the compressor or protections.
•
Use supplementing flexible pipe to connect refriger-
ant cylinder, pressure gauge and outdoor unit. And
The refrigerant should be charged in liquid state.
Before recharging, The air in the flexible pipe and
manifold gauge should be exhausted.
•
After finished refrigerant recharge process, check
whether there is refrigerant leakage at the connec-
tion joint part.(Using gas leakage detector or soap
water to detect).
9. Engineering of Insulation
9.1 Insulation of refrigerant pipe
1. Operational procedure of refrigerant pipe
insulation
Cut the suitable pipe
→
insulation (except joint section)
→
flare the pipe
→
piping layout and connection
→
vacuum
drying
→
insulate the joint parts
2. Purpose of refrigerant pipe insulation
•
During operation, temperature of gas pipe and
liquid pipe shall be over-heating or over-cooling
extremely. Therefore, it is necessary to carry out in-
sulation; otherwise it shall debase the performance
of unit and burn compressor.
•
Gas pipe temperature is very low during cooling.
If insulation is not enough, it shall form dew and
cause leakage.
•
Temperature of gas pipe is very high (generally
50-100
℃
) during heating. Insulation work must be
carried out to prevent hurt by carelessness touching.
3. Insulation material selection for refrigerant pipe
•
The burning performance should over 120
℃
•
According to the local law to choose insulation
materials
•
The thickness of insulation layer shall be above
10mm.If in hot or wet environment place, the layer
of insulation should be thicker accordingly.
4. Installation highlights of insulation construction
•
Gas pipe and liquid pipe shall be insulated sepa-
rately, if the gas pipe and liquid pipe were insulated
together; it will decrease the performance of air
conditioner.
•
The insulation material at the joint pipe shall be
5~10cm longer than the gap of the insulation mate-
rial.
•
The insulation material at the joint pipe shall be
inserted into the gap of the insulation material.
•
The insulation material at the joint pipe shall be
banded to the gap pipe and liquid pipe tightly.
•
The linking part should be use glue to paste to-
gether
•
Be sure not bind the insulation material over-tight, it
may extrude out the air in the material to cause bad
Содержание YDAX-035H-09M25
Страница 11: ...Page 11 3 Dimensional Drawings Indoor Unit Compact Cassette...
Страница 13: ...Page 13 Outdoor Unit YDAX 035H 09M25...
Страница 14: ...Page 14 YDAX 050H 09M25...
Страница 15: ...Page 15 YDAX 070H 09M25...
Страница 16: ...Page 16 YDAX 100H 09M25 YDAX 100H 09T35 YDAX 140H 09T35...
Страница 17: ...Page 17 YDAX 140H 09T35...
Страница 19: ...Page 19 12K 18K 24K 55K...
Страница 27: ...Page 27 YDAX 035H 09M25 YDAX 050H 09M25...
Страница 28: ...Page 28 YDAX 070H 09M25...
Страница 29: ...Page 29 YDAX 100H 09M25...
Страница 30: ...Page 30 YDAX 100H 09T35 YDAX 140H 09T35...
Страница 35: ...Specifications Page 35 12K Heating airflow velocity distributions Heating temperature distributions...
Страница 37: ...Specifications Page 37 12K Heating airflow velocity distributions Heating temperature distributions...
Страница 39: ...Specifications Page 39 18K Heating airflow velocity distributions Heating temperature distributions...
Страница 41: ...Specifications Page 41 18K Heating airflow velocity distributions Heating temperature distributions...
Страница 55: ...Page 55 55K Discharge Angle 30 Heating airflow velocity distributions Heating temperature distributions...
Страница 57: ...Page 57 55K Discharge Angle 60 Heating airflow velocity distributions Heating temperature distributions...
Страница 92: ...Specifications Page 92 12k 18k 24k 30k...
Страница 93: ...Specifications Page 93 36k 42k 48k 55k...
Страница 95: ...Page 95 YDAX 070H 09M25 YDAX 100H 09M25 YDAX 100H 09T35...
Страница 96: ...Page 96 YDAX 140H 09T35...
Страница 105: ...Product Features Page 105 Remote LCD Screen Indicators...