Installation instruction
For installation, please review the items below:
•
Is the connected units quantity and the total capacity in the allowable range?
•
Is the refrigerant pipe length in the limited range?
•
Is the pipe size proper? And if the pipe is installed horizontally?
•
Is the branch pipe installed horizontally or vertically?
•
Is the additional refrigerant counted correctly and weighed by the standard balance?
•
Is there refrigerant leakage?
•
Can all the indoor power supplies be on/off simultaneously?
•
Is the power voltage in compliance with the data marked on the rating label?
•
Have the address of indoor units, VP units and outdoor units been set?
(1) Before installation
1) Before installation, check respectively if the model, power supply, pipe, wires and parts
purchased are correct.
2) Check if the indoors and outdoors can be combined as the following.
Before installation, read the manual for outdoors, indoors and VP units.
Outdoor
Indoor
Gather pipe
Capacity
(100W)
Combination type
Indoor Qty
Total indoor
capacity (kBtu/h)
280
Single (10HP)
16
140-364
335
Single (12HP)
19
167-436
400
Single (14HP)
23
200-520
450
Single (16HP)
26
225-585
560
Combination (280+280)
33
280-728
TAS20HR
615
Combination (335+280)
36
307-800
TAS20HR
680
Combination (400+280)
39
340-884
TAS20HR
730
Combination (450+280)
43
365-949
TAS20HR
800
Combination (400+400)
46
400-1040
TAS20HR
850
Combination (400+450)
50
425-1105
TAS20HR
900
Combination (450+450)
53
450-1170
TAS20HR
960
Combination (400+280+280)
56
480-1248
TAS30HR
1010
Combination (450+280+280)
59
505-1313
TAS30HR
1080
Combination (280+400+400)
63
540-1404
TAS30HR
1130
Combination (400+280+450)
64
565-1469
TAS30HR
1180
Combination (450+450+280)
64
590-1534
TAS30HR
1235
Combination (335+450+450)
64
617-1606
TAS30HR
1300
Combination (400+450+450)
64
650-1690
TAS30HR
1350
Combination (450+450+450)
64
675-1755
TAS30HR