![Airwell YAF018 Скачать руководство пользователя страница 39](http://html1.mh-extra.com/html/airwell/yaf018/yaf018_service-manual_2879929039.webp)
12-8
CONTROL SYSTEM
SM HAFRPM 2-A.1 GB
12.4.2 Cooling
Mode: Cool, Auto (at Cooling)
Temp: Selected desired temperature.
Fan: HIGH,
MED,
LOW
Timer: Any
I Feel: On or Off
Control function
Maintains room temp at desired level by comparing RT and SPT.
(RT - SPT) [
o
c]
+3
+2
+1
0
-1
-2
ON
OFF
ON
OFF
USER FAN SPEED
ON
OFF
COMP
OFAN
IFAN
RV
Note:
1) IFAN is always running at High, Medium or Low speed selected by user.
2) In IFEEL mode, the Room Temperature (RT) is the RCT from a R/C. Otherwise,
the RT is the RAT from the Room Thermistor.
Содержание YAF018