7
REMINDER
ANTIFREEZE MANDATORY
Protection system complying with STANDARD to be provided.
Pt=Total capacity Ps=Sensible capacity
Water mode
Inlet air temperature
Ventilation speed
Relative humidity
PV
MV
GV
603 m3/h
753 m3/h
873 m3/h
27°c
Pt
kW
2.620
2.086
3.332
47%
Ps
1.956
2.287
2.481
6°c / 11°c
25°c
Pt
kW
2.127
2.516
2.719
50%
Ps
1.675
1.958
2.133
23°c
Pt
kW
1.643
1.840
1.996
50%
Ps
1.471
1.668
1.824
27°c
Pt
kW
2.309
2.721
2.936
47%
Ps
1.823
2.126
2.313
7°c / 12°c
25°c
Pt
kW
1.841
2.181
2.358
50%
Ps
1.554
1.813
1.978
23°c
Pt
kW
1.484
1.663
1.753
50%
Ps
1.401
1.593
1.720
27°c
Pt
kW
2.023
2.386
2.574
47%
Ps
1.703
1.982
2.159
8°c / 13°c
25°c
Pt
kW
1.640
1.890
2.044
50%
Ps
1.470
1.693
1.847
23°c
Pt
kW
1.341
1.509
1.595
50%
Ps
1.341
1.509
1.595
27°c
Pt
kW
1.585
1.849
1.997
47%
Ps
1.528
1.766
1.932
10°c / 15°c
25°c
Pt
kW
1.338
1.507
1.594
50%
Ps
1.338
1.507
1.594
23°c
Pt
kW
1.102
1.243
1.315
50%
Ps
1.102
1.243
1.315
Water mode
Inlet air temperature
Ventilation speed
PV
MV
GV
658 m3/h
774 m3/h
857 m3/h
40°c / 30°c
19°c
Pt
kW
1.684
1.925
2.041
20°c
Pt
kW
1.565
1.787
1.863
21°c
Pt
kW
1.444
1.648
1.718
45°c / 35°c
19°c
Pt
kW
2.452
2.933
3.111
20°c
Pt
kW
2.296
2.752
2.919
21°c
Pt
kW
2.142
2.568
2.724
50°c / 40°c
19°c
Pt
kW
3.239
3.856
4.091
20°c
Pt
kW
3.091
3.683
3.905
21°c
Pt
kW
2.942
3.505
3.719
UNIT WITHOUT VALVE , WITH ELECTRIC HEATING 1590 W
Содержание XLM OG 18
Страница 2: ......
Страница 10: ...8 CURVE OF PRESSURE DROP 0 5 10 15 20 25 30 35 0 100 200 300 400 500 600 700 800 l h PDC kPa...
Страница 16: ...14 ELECTRICAL CONNECTIONS...
Страница 24: ...22...
Страница 25: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO...
Страница 26: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO II...
Страница 28: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO IV...
Страница 29: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO V OPTIONS OPTIONS OPTIONEN OPCIONES OPZIONI 18 50...
Страница 36: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XII...