7-1
ELECTRICAL DATA
SM TRIO52 1-A.2 GB
7.
ELECTRICAL DATA
7.1
Single Phase Units
MODEL
TRIO 5.2 kW DAKOTA
Power Supply
1 PH, 220-240 VAC, 50/60Hz
Connected to
DAKOTA WDI 7, 9 and 12
Maximum Current
9.4 A
Inrush Current*
35 A
Starting Current**
10.5 A
Circuit breaker
20 A
Power supply wiring - No. x cross section, mm
2
3 X 2.5
Interconnecting cable - No. x cross section, mm
2
4 X 1.5
Note:
*
Inrush current is the current when power is up. (charging the DC capacitors at outdoor unit
controller).
** Starting current is the current when starting the compressor
NOTE
Power wiring cord should comply with local lows and electrical regulations
requirements.
CONTENTS